Honeywell HC900 User And Installation Manual page 129

Process and safety controller
Hide thumbs Also See for HC900:
Table of Contents

Advertisement

32 point DC Output Wiring
The DC digital Output module provides 32 externally powered outputs in 2 groups of 16 (Figure 62). The
outputs are high side switching (current sourcing) type. Over-current protection is provided for each
channel, in 4 groups of 8 channels. In case of short circuit for any output channel, that whole group of 8 is
switched off. Power cycling is not required to reset the module. SIL applications require an external series
relay used to ensure outputs achieve failsafe action. See HC900 Process & Safety Controller Safety Manual
for additional details.
A green LED on the module provides indication of an ON state for each output.
Requires Low Voltage Euro style 36-terminal terminal block.
AC Output Module Wiring
The AC Output Module provides eight output circuits. Each output is isolated from the other outputs. An
example of AC output wiring is shown in Figure 63. Specifications for this module and for other modules
are given in the Specifications manual. SIL applications require an external series relay used to ensure
outputs achieve failsafe action. See HC900 Process & Safety Controller Safety Manual for additional
details.
Revision 6
21 April 2017
Figure 62 – 32 point DC Output Module Wiring
HC900 Process & Safety Controller User and Installation Manual
115