Honeywell HC900 User And Installation Manual page 224

Process and safety controller
Hide thumbs Also See for HC900:
Table of Contents

Advertisement

CE Conformity
ATEX
ABS Type Approval
General Purpose
Safety
Hazardous
(Classified) Location
Safety
Module Temperature
Classifications
Redundancy Switch Module (RSM)
210
This product is in conformity with the protection requirements of the following European
Council Directives: 2006/95/EC, the Low Voltage Directive, and 2004/108/EC
, the EMC Directive. Conformity of this product with any other "CE Mark" Directive(s) shall not
be assumed. EN61326: Electrical Equipment For Measurement, Control and Laboratory use.
EMC requirements.
The apparatus fulfills the requirements for Group II, Category 3 equipment in accordance with
Directive 94/9/EC.
Certificate of Design Assessment - No. 06-HS186538-4-PDA (June 2014.)
No. 06-BA766694-X (York Location)
No. BY1100081X (Pune Location)
HC900 control system is NOT to be used for direct propulsion, steering, navigation or safety
systems. The controller must be installed in a grounded metal enclosure and must not be
used in non-weather protected spaces. Each application is to be approved on a case by case
basis.
Compliant with EN61010-1, UL, UL 61010-1 2
FM Class I, Div. 2, Groups A, B, C, D
CSA Class I, Div. 2 Groups A, B, C, D
Class 1, Zone 2, IIC
Module Type
Redundant CPU Rack
Redundant PS Ext. Rack
8 Slot Redundant PS Ext. Rack
12 Slot Redundant PS Ext. Rack
4 I/O Slot Rack
8 I/O Slot Rack
12 I/O Slot Rack
Power Supply (P01)
Power Supply (P02)
Power Supply (P24)
Power Status Module (PSM)
C30/C50/C70/C75 CPU
Scanner 1
HC900 Process & Safety Controller User and Installation Manual
Approvals
nd
edition, CSA C22.2 No. 1010-1
"T"
Module Type
Rating
T6
Scanner 2
T5
Analog Input (8 channels)
T6
Analog Input (16 chan)
T6
Analog Output (4 chan)
Analog Output (8 chan)
T6
Analog Output (16 channel)
T6
Digital Input, Contact type (16 chan)
T6
Digital Input, 24 Vdc (16 chan)
T4
Digital Input, 120/240 Vac (16 chan)
Digital Input 120/240VAC, 125VDC
(16 Channel)
T4
Digital Input Vdc (32 chan)
T4
Digital Output, Relay type (8 chan)
T6
Digital Output, 24 Vdc, (16 chan)
T4
Digital Output, 120/240 Vac (8 chan)
T6
Digital Output Vdc (32 chan)
T4
Pulse/Frequency/Quadrature (4 chan)
"T"
Rating
T4
T6
T6
T4
T4
T3C
T5
T4
T3C@ Ta= 60 deg. C
T4 @ Ta = 40 deg. C
T3@Ta=60 deg. C
T4@Ta=40 deg. C
T3@Ta=60 deg. C
T4@Ta=40 deg. C
T5
T4
T4
T6
T5
Revision 6
21 April 2017

Advertisement

Table of Contents
loading