Advertisement

Number
Possible Causes
of Red
Strobes
6
High temperature
condition in a Scanner
2 rack has been
detected.
6
Scanner 2 has a CPU
or Memory diagnostic.
7
A Scanner 2 rack has
a bad power supply.
180
Lead and/or Reserve Controller
Action(s)
1. Associated AI blocks that are
configured as T/Cs set their fail pin
on, their warn pin off, and their
output pin to the failsafe value.
2. Associated AI blocks that are
configured as T/Cs set their IO
status to either:
"CJ High Temperature" if one of
the two CJs on an AI card is
indicating a temperature greater
than 70 degrees C
"CJ Failure" if both CJ sensors are
failing to convert.
3. Associated rack monitor block's
module fail pin is turned on.
4. Associated rack monitor block's
RACK OK pin is turned off.
5. Associated rack monitor block's
HITEMP pin is turned on.
6. ASYS and FSYS blocks' HITEMP
pins are turned on.
7. ASYS and FSYS blocks' HW OK
pins are turned off.
1. Associated rack monitor block's
RACK OK pin is turned off.
2. ASYS and FSYS blocks' HW
OK pins are turned off.
1. Associated rack monitor block's
RACK OK pin is turned off.
2. ASYS and FSYS blocks' HW
OK pins are turned off.
HC900 Process & Safety Controller User and Installation Manual
User Action
Locate the Scanner 2 that indicates a
bad power-supply diagnostic, and
replace the defective supply.
Honeywell OI
HCDesigner/HC
Indication
Utilities Indication
See CPU or
See CPU or
Memory in "Rack
MEMORY in the
associated rack's
Diagnostics"
"Rack Diagnostics
dialog box.
Overview" display.
See POWER
See Power
SUPPLY
Supply
DIAGNOSTICS in
Diagnostics in
"Rack
the associated
rack's "Rack
Diagnostics"
Diagnostics
dialog box.
Overview" display.
Revision 6
21 April 2017