Vega VEGAPULS 62 Operating Instructions Manual page 56

Universally implementable radar level transmitter for continuous level 4...20 ma/hartmeasurement of liquids
Hide thumbs Also See for VEGAPULS 62:
Table of Contents

Advertisement

Output variable
Output signal
Resolution
Fault signal
Current limitation
Load
Integration time (63% of the input
variable)
Rise time
Fulfilled Namur recommendation
Input variable
Parameter
Min. distance from antenna end
Recommended meas. range depending on the antenna diameter
- ø 40 mm (1.6 in)
- ø 48 mm (1.9 in)
- ø 75 mm (3 in), ø 95 mm (3.7 in),
parabolic antenna
Accuracy (similar to DIN EN 60770-1)
Reference conditions acc. to DIN EN 61298-1
- temperature
- relative humidity
- pressure
VEGAPULS 62 - 4 ... 20 mA/HART
4 ... 20 mA/HART
1.6 µA
current output unchanged, 20.5 mA,
22 mA, < 3.6 mA (adjustable)
22 mA
see load diagram in Power supply
0 ... 999 s, adjustable
150 ms (ti: 0 s, 0 ... 100 %)
NE 43
distance between process fitting and
product surface
50 mm (2 in)
up to 10 m (33 ft)
up to 15 m (50 ft)
up to 30 m (98.4 ft)
18 ... 30°C (64 ... 86°F)
45 ... 75 %
860 ... 1060 mbar (86 ... 106 kPa or 12.5 ...
15.4 psi)
Supplement
55