Vega VEGAPULS 62 Operating Instructions Manual page 18

Universally implementable radar level transmitter for continuous level 4...20 ma/hartmeasurement of liquids
Hide thumbs Also See for VEGAPULS 62:
Table of Contents

Advertisement

Installation location
VEGAPULS 62 - 4 ... 20 mA/HART
When mounting VEGAPULS 62, keep a distance of at
least 200 mm (7.9 in) to the vessel wall. If the sensor is
installed in the center of concave or arched vessel tops,
multiple echoes can arise. These can, however, be
faded out by an appropriate adjustment (see Setup).
If this distance cannot be maintained, a false echo
storage should be carried out during setup. This applies
particularly if buildup on the vessel wall is expected. In
this case, we recommend repeating the false echo
storage later on with existing buildup.
1
> 200 mm
Fig. 6: Mounting on arched vessel tops
1
Reference plane
2
Vessel center or symmetry axis
In vessels with conical bottom it can be advantageous to
mount the sensor in the center of the vessel, as
measurement is then possible down to the lowest points
of the vessel bottom.
Mounting
2
17