Vessel form
Damping
VEGAPULS 62 - 4 ... 20 mA/HART
Setup with the indicating and adjustment module PLICSCOM
With the medium selection, the sensor is adapted
perfectly to the product and the reliability, particularly in
products with bad reflective properties is considerably
increased.
Enter the requested parameter via the respective keys,
save your settings and jump to the next menu item with
the [–>] key.
Apart from the medium also the vessel form can
influence the measurement. To adapt the sensor to
these conditions, this menu item offers (depending on
either liquid or solid is selected) different options. For
Liquid these are Storage tank, Stilling tube, Open vessel
or Stirred vessel, for Solid Silo or Bunker.
Vessel form
Storage tank
Enter the requested parameter via the respective keys,
save your settings and jump to the next menu item with
the [–>] key.
To suppress fluctuation in the measured value display,
e.g. by agitated product surfaces, an integration time
can be set. This time can be between 0 and 999
seconds. Please note that the reaction time of the entire
measurement will be longer and the sensor will react to
quick changes of the measured value with a corre-
sponding delay. In general, a time of a few seconds is
sufficient to smooth the measured value display.
Damping
0 s
Enter the requested parameter via the respective keys,
save your settings and jump to the next menu item with
the [–>] key.