Sensor orientation
VEGAPULS 62 - 4 ... 20 mA/HART
Fig. 9: Recommended socket mounting
If the reflective properties of the medium are good, you
can mount VEGAPULS 62 on socket pieces higher than
the antenna length. You will find recommended values of
the socket heights in the following illustration. The
socket end should be smooth and burr-free, if possible
also rounded. Carry out a false echo storage afterwards.
Fig. 10: Deviating socket dimensions
In liquids, direct the sensor as close as vertical to the
product surface to achieve an optimum measurement.
d
1½"
50 mm/2"
80 mm/3"
100 mm/4"
d
150 mm/6"
Mounting
h
max.
200 mm
250 mm
300 mm
500 mm
800 mm