Setup with the indicating and adjustment module PLICSCOM
Carrying out max. adjust-
ment
Medium selection
38
5 Save the settings with [OK] and move to max.
adjustment with [–>].
Proceed as follows:
Max. adjustment
100.00 %
=
1.000 m(d)
2.000 m(d)
1 Prepare the percentage value for editing with [OK]
and set the cursor to the requested position with [–>].
Set the requested percentage value with [+] and
save with [OK]. The cursor jumps now to the
distance value.
2 Enter the appropriate distance value in m (corre-
sponding to the percentage value) for the full vessel.
Make sure that the max. level must be beneath the
dead zone.
3 Save the settings with [OK] and move to the medium
selection with [–>].
Each product has different reflective properties. In
liquids additional interfering factors are fluctuating
product surfaces and foam generation. In solids, this is
the dust generation, material cone and additional
echoes caused by the vessel wall. To adapt the sensor
to the different applications, you should choose in this
menu item Liquid or Solid.
Medium
Liquid
According to the conductivity and the dielectric constant
value of liquids, the reflection properties can differ
considerably. Therefore additional option such as
Solvent, Chem. mixture and Water based are offered
below the menu item Liquid.
For solids you choose also Powder/Dust, Granular/
Pellets or Ballast/Pebbels.
VEGAPULS 62 - 4 ... 20 mA/HART