GE 269Plus Instruction Manual page 70

Motor management relay
Table of Contents

Advertisement

ACTUAL VALUES MODE
Table 3–2: 269Plus ACTUAL VALUES (Sheet 8 of 9)
PAGE
LINE INFORMATION LINE
6
8
LEARNED Start Capacity
Last Start T.C. = XXX %
6
9
LEARNED Start Capacity
required = XX PERCENT
3
6
10
END OF PAGE SIX
ACTUAL VALUES
ACTUAL VALUES PAGE 7: METERING DATA
7
1
PAGE 7: ACTUAL VALUES
METERING DATA
7
2
METER MODULE
NOT INSTALLED
7
3
PHASE TO PHASE
VOLTAGE CONNECTION
7
3 †
PHASE TO NEUTRAL
VOLTAGE CONNECTION
7
4
Vab = XXXX
Vca = XXXX
7
4 †
Van = XXXX
Vcn = XXXX
7
5 †
3 PHASE KWATTS
KW = +XXXXX
† Available only if a meter is online.
‡ Messages not shown if the answer to
3-
14
Courtesy of NationalSwitchgear.com
DESCRIPTION
Learned motor thermal capacity used since last
start. See 3.21: THERMAL CAPACITY ALARM on
page 3–59 for details on using this value to adapt
the relay to the motor.
Learned motor thermal capacity used on start. This
value is learned after 5 successful starts. The start
thermal capacity for each of the last five starts are
added together and divided by 4. This allows a
margin of 24% to be built into the value. Each start is
limited between 10% and 70% of the thermal
capacity used on start.
This learned parameter is used with the start inhibit
function on Setpoints page 5. See Section 3.21:
THERMAL CAPACITY ALARM for details.
Last line of page 6.
ACTUAL VALUES page 7 header
Appears if meter not on-line (see Setpoints page 7,
line 2)
Appears whether or not the meter is online. When
the meter is online, this message displays the VT
configuration as connected to the meter. See the
figures on pages 2–31 to 2–37 for details.
This message is displayed when the meter's VTs are
wired to measure for phase to phase voltage.
This message is displayed when the meter's VTs are
wired for phase to neutral voltage measurement.
Appears whether or not the meter is online. Three
Vbc = XXXX
phase to phase voltages are displayed when the VT
AVG.= XXXX V
configuration above is phase to phase.
Three phase to neutral voltages are displayed only
Vbn = XXXX
when the VT configuration is phase to neutral.
AVG.= XXXX V
Positive or negative 3 phase kwatts. See Figure 3–8:
POWER MEASUREMENT CONVENTIONS.
A R E T H E R E A N Y R T D S C O N N E C T E D ?
269Plus Motor Management Relay
3 SETUP AND USE
is
(located on Setpoints page 2, line 3).
N O