GE 269Plus Instruction Manual page 80

Motor management relay
Table of Contents

Advertisement

SETPOINTS MODE
TABLE 3–3: 269PLUS SETPOINTS (SHEET 7 OF 25)
PAGE
LINE INFORMATION LINE
2
32
END OF PAGE TWO
SETPOINT VALUES
SETPOINTS PAGE 3: O/L CURVE SETPOINTS
3
1
PAGE 3: SETPOINT VALUES
O/L CURVE SETPOINTS
3
2
CUSTOM CURVE?
3
YES voids selected curve
3
3
SELECTED CURVE NUMBER
CURVE # = X
3
3
Check all custom curve
entries before exiting
3
4
TRIP TIME @ 1.05 X FLC
3
5
TRIP TIME @ 1.10 X FLC
3
6
TRIP TIME @ 1.20 X FLC
3
7
TRIP TIME @ 1.30 X FLC
3
8
TRIP TIME @ 1.40 X FLC
3
9
TRIP TIME @ 1.50 X FLC
3
10
TRIP TIME @ 1.75 X FLC
3
11
TRIP TIME @ 2.00 X FLC
3
12
TRIP TIME @ 2.25 X FLC
3-
24
Courtesy of NationalSwitchgear.com
XXX
=
XXXXX SECONDS
=
XXXXX SECONDS
=
XXXXX SECONDS
=
XXXXX SECONDS
=
XXXXX SECONDS
=
XXXXX SECONDS
=
XXXXX SECONDS
=
XXXXX SECONDS
=
XXXXX SECONDS
269Plus Motor Management Relay
NOTE: Lines 4 through 25 are not seen when
using a standard curve.
Range: 1 to 8 step 1
Factory Value = 4; Manual Reference: 3.20
Range: 1 to 8 step 1
Factory Value = 4; Manual Reference: 3.20
This line is not seen when using a custom curve.
This line is not seen when using a standard curve
Range: 1 to 12000 sec., step 1
Manual Reference: 3.20
This line is not seen when using a standard curve
Range: 1 to 12000 sec., step 1
Manual Reference: 3.20
This line is not seen when using a standard curve
Range: 1 to 12000 sec., step 1
Manual Reference: 3.20
This line is not seen when using a standard curve
Range: 1 to 12000 sec., step 1
Manual Reference: 3.20
This line is not seen when using a standard curve
Range: 1 to 12000 sec., step 1
Manual Reference: 3.20
This line is not seen when using a standard curve
Range: 1 to 12000 sec., step 1
Manual Reference: 3.20
This line is not seen when using a standard curve
Range: 1 to 2000 sec., step 1
Manual Reference: 3.20
This line is not seen when using a standard curve
Range: 1 to 2000 sec., step 1
Manual Reference: 3.20
This line is not seen when using a standard curve
Range: 1 to 2000 sec., step 1
Manual Reference: 3.20
This line is not seen when using a standard curve