SETPOINTS MODE
TABLE 3–3: 269PLUS SETPOINTS (SHEET 25 OF 25)
PAGE
LINE INFORMATION LINE
7
24
POWER FACTOR TRIP
TIME DELAY = XXX
This line sets the time that a power factor trip condition must persist to facilitate a trip.
Range: 1 to 255 seconds in steps of 1 sec.
Factory Value = 5 seconds
7
25
POSITIVE KVAR ALARM
LEVEL = +XXXXX KVARS
3
This setpoint is used to set the positive KVAR limit threshold for a kvar alarm condition.
Range: 100 to 25000 KVARS or OFF, in steps of 100
Factory Value = OFF
7
26
NEGATIVE KVAR ALARM
LEVEL = -XXXXX KVARS
This setpoint is used to set the negative KVAR limit threshold for a kvar alarm condition.
Range: 100 to 25000 KVARS or OFF, in steps of 100
Factory Value = OFF
7
27
KVAR ALARM
TIME DELAY = XXX SEC
This setpoint is used to set the time that a KVAR alarm condition must persist for in order to
facilitate an alarm.
Range: 1 to 255 seconds in steps of 1 sec.
Factory Value = 5 seconds
7
28
ENABLE VOLTAGE PHASE
REVERSAL?
This line enables or disables the phase reversal trip feature as detected from the meter
monitoring the line voltages.
Range: YES - enable voltage phase reversal; NO - disable voltage phase reversal
7
29
ANALOG OUT SCALE FACTOR
100KWxXXX
This line sets the full scale value for the meter's analog output (kW and kvars).
Range: 1 to 255 in steps of 1. Factory Value = 1
7
30
END OF PAGE SEVEN
SETPOINT VALUES
3-
42
Courtesy of NationalSwitchgear.com
XXX
30KVARxXXX
269Plus Motor Management Relay