GE 269Plus Instruction Manual page 76

Motor management relay
Table of Contents

Advertisement

SETPOINTS MODE
TABLE 3–3: 269PLUS SETPOINTS (SHEET 3 OF 25)
PAGE
LINE INFORMATION LINE
1
30
IMMEDIATE OVERLOAD
LEVEL = X.XX x FLC
1
31
END OF PAGE ONE
SETPOINT VALUES
SETPOINTS PAGE 2: RTD SETPOINTS
2
1
PAGE 2: SETPOINT VALUES
3
RTD SETPOINTS
2
2
RTD SENSOR TYPE
TYPE = 100 OHM PLATINUM
2
3
ARE THERE ANY RTDs
CONNECTED?
2
4
RTD MESSAGE DISPLAY = C
(C:CELSIUS/F:FAHRENHEIT)
2
5
# OF STATOR RTDS USED
# OF RTDs = X
2
6
STATOR #1 ALARM LEVEL
=
RTD #1 ALARM LEVEL
=
2
7
STATOR #1 HIGH ALARM
LEVEL =
RTD #1 HIGH ALARM
LEVEL =
2
8
STATOR #1 TRIP LEVEL
=
RTD #1 TRIP LEVEL
=
3-
20
Courtesy of NationalSwitchgear.com
XXX
XXX DEGREES C
or
XXX DEGREES C
XXX DEGREES C
or
XXX DEGREES C
XXX DEGREES C
or
XXX DEGREES C
269Plus Motor Management Relay
Range: 1.01 to 1.50 ×FLC or OFF, in steps of 0.01
Factory Value = OFF; Manual Reference: 3.17
Range: 100 OHM PLATINUM, 10 OHM COPPER,
100 OHM NICKEL, 120 OHM NICKEL.
Displays the RTD type accepted by the relay. To
change, contact the factory. Manual Reference: 3.18
Range: YES or NO
If set to
, RTD messages in Setpoints and Actual
N O
Values are not displayed. If no RTDs are connected
and Alarm and Trip levels are set, trips will occur.
Factory Value = YES; Manual Reference: 3.18
Range C (° Celsius) or F (° Fahrenheit)
Factory Value = C; Manual Reference: 3.18
Range: 0 to 6 in steps of 1
Factory Value = 6; Manual Reference: 3.18
Range: 0 to 200°C or OFF, in steps of 1°C
(32 to 392°F in steps of 1°F if Fahrenheit)
Factory Value = OFF; Manual Reference: 3.18
Range: 0 to 200°C or OFF, in steps of 1°C
(32 to 392°F in steps of 1°F if Fahrenheit)
Factory Value = OFF; Manual Reference: 3.18
Range: 0 to 200°C or OFF, in steps of 1°C
(32 to 392°F in steps of 1°F if Fahrenheit)
Factory Value = OFF; Manual Reference: 3.18
Range: 0 to 200°C or OFF, in steps of 1°C
(32 to 392°F in steps of 1°F if Fahrenheit)
Factory Value = OFF; Manual Reference: 3.18
Range: 0 to 200°C or OFF, in steps of 1°C
(32 to 392°F in steps of 1°F if Fahrenheit)
Factory Value = OFF; Manual Reference: 3.18
Range: 0 to 200°C or OFF, in steps of 1°C
(32 to 392°F in steps of 1°F if Fahrenheit)
Factory Value = OFF; Manual Reference: 3.18
3 SETUP AND USE
GE Power Management