SETPOINTS MODE

TABLE 3–3: 269PLUS SETPOINTS (SHEET 1 OF 25)
PAGE
LINE INFORMATION LINE
SETPOINTS PAGE 1: MOTOR AMPS SETPOINTS
1
1
PAGE 1: SETPOINT VALUES
MOTOR AMPS SETPOINTS
1
2
PHASE CT RATIO
CT SECONDARY = X AMP
1
3
PHASE CT RATIO
3
CT PRIMARY = XXXX:X
1
4
MOTOR FULL LOAD CURRENT
FLC=
1
5
LEVEL = 1.05 x FLC
1
6
ACCEL.TIME= XXX.X SECONDS
Consult motor data sheet
1
7
STARTS/HOUR= X
Consult motor data sheet
1
8
UNBALANCE ALARM LEVEL
U/B ALARM=
1
9
U/B ALARM TIME DELAY
TIME DELAY =
1
10
UNBALANCE TRIP LEVEL
U/B TRIP=
1
11
U/B TRIP TIME DELAY
U/B DELAY= XXX SECONDS
1
12
G/F CT RATIO :5 ? XXX
(NO indicates 2000:1)
1
13
GROUND CT PRIMARY
GROUND CT =
1
14
GROUND FAULT ALARM LEVEL
G/F ALARM=
3-
18
Courtesy of NationalSwitchgear.com
XXXX AMPS
O/L PICKUP LEVEL
XX PERCENT
XXX SEC
XX PERCENT
XXX:5
XXX AMPS
269Plus Motor Management Relay
Range: 1, 5
Factory Value: 5; Manual Reference: 3.7
Range: 20 to 1500 in steps of 1
Factory Value: 100; Manual Reference: 3.7
Range: 10 to 1500 A in steps of 1
Factory Value: 10 A; Manual Reference: 3.7
Range: 1.05 to 1.25 x FLC in steps of 0.01
Factory Value: 1.05 x FLC
Manual Reference: 3.18, 3.20
Range: 0.5 to 125.0 seconds or OFF in steps of 0.5
Factory Value = 10.0 sec.; Manual Reference: 3.8
Range: 1 to 5 starts or OFF in steps of 1
Factory Value = 3; Manual Reference: 3.9
Range: 4 to 30% or OFF in steps of 1%
Factory Value = 10%; Manual Reference: 3.10
Range: 3 to 255 in steps of 1 second
Factory Value = 5 sec.; Manual Reference: 3.10
Range: 4 to 30% or OFF in steps of 1%
Factory Value = 15%; Manual Reference: 3.10
Range: 3 to 255 seconds in steps of 1
Factory Value = 5 sec.; Manual Reference: 3.10
Range: YES (5 A secondary), NO (GE Power
Management 50:0.025 A CT with ratio of 2000:1)
Factory Value: NO; Manual Reference: 3.11
Range: 20 to 1500 in steps of 1
(Not seen if ratio is 2000:1)
Factory Value = 100; Manual Reference: 3.11
Range: For 50:0.025A (2000:1 ratio) CT, 1.0 to 10 A
or OFF, in steps of 1
Factory Value = 4 A; Manual Reference: Section 3.11