Table : 3-3 269P Lus Setpoints - GE 269Plus Instruction Manual

Motor management relay
Table of Contents

Advertisement

3 SETUP AND USE
TABLE 3–3: 269PLUS SETPOINTS (SHEET 2 OF 25)
PAGE
LINE INFORMATION LINE
1
15
GROUND FAULT ALARM LEVEL
G/F ALARM= XXX xCT
1
16
G/F ALARM TIME DELAY
TIME DELAY =
1
17
GROUND FAULT TRIP LEVEL
G/F TRIP =
1
18
GROUND FAULT TRIP LEVEL
G/F TRIP =
1
19
G/F TRIP TIME DELAY
G/F DELAY= XX.X SECONDS
1
20
UNDERCURRENT ALARM LEVEL
U/C ALARM=
1
21
UNDERCURRENT ALARM DELAY
TIME DELAY=
1
22
UNDERCURRENT TRIP LEVEL
U/C TRIP =
1
23
UNDERCURRENT TRIP DELAY
TIME DELAY=
1
24
MECHANICAL JAM ALARM
ALARM LEVEL= XXX xFLC
1
25
MECH. JAM ALARM TIME
DELAY = XXX.X SECONDS
1
26
RAPID TRIP / MECH. JAM
TRIP LEVEL=
1
27
RAPID TRIP TIME DELAY
DELAY= XXX.X SECONDS
1
28
SHORT CIRCUIT TRIP LEVEL
S/C TRIP= XX x FLC
1
29
SHORT CIRCUIT TIME DELAY
S/C DELAY= XX.X SECONDS
GE Power Management
Courtesy of NationalSwitchgear.com
Range: For 5 A secondary CT, 0.1 to 1.0 x CT rating
or OFF, in steps of 0.1 (not seen if ratio is 2000:1)
Factory Value = 0.4 x CT; Manual Reference: 3.12
Range: 1 to 255 seconds in steps of 1
Factory Value = 10 seconds; Manual Reference: 3.11
XXX SEC
Range: For 50:0.025A (2000:1 ratio) CT, 1.0 to 10.0 A
or OFF, in steps of 1 A
XXX AMPS
Factory Value = 8; Manual Reference: Section 3.11
Range: For 5 A secondary CT, 0.1 to 1.0 x CT rating
or OFF, in steps of 0.1 (not seen if ratio is 2000:1)
XX xCT
Factory Value = 0.8; Manual Reference: Section 3.11
Range: 0.0 (Instantaneous) to 20.0 seconds in steps
of 0.5. Additional time delay of 0.25 sec. after 20.0.
Factory Value = 0.0 sec.; Manual Reference: 3.11
Range: 1 to 1000 amps or OFF, in steps of 1 A
Factory Value = OFF; Manual Reference: 3.12
XXXX AMPS
Range: 1 to 255 seconds in steps of 1
Factory Value = 10 sec.; Manual Reference: 3.12
XX SECONDS
Range: 1 to 1000 amps or OFF, in steps of 1
Factory Value = OFF; Manual Reference: 3.12
OFF AMPS
Range: 1 to 255 seconds in steps of 1
Factory Value = 5 sec.; Manual Reference: 3.12
XXX SECONDS
Range: 1.5 to 6.0 × FLC or OFF, in steps of 0.5
Factory Value = OFF; Manual Reference: 3.13
Range: 0.5 to 125.0 seconds in steps of 0.5
Factory Value = 5.0; Manual Reference: 3.13
Range: 1.5 to 6.0 × FLC or OFF, in steps of 0.5
Factory Value = 2.5 × FLC; Manual Reference: 3.13
X.X x FLC
Range: 0.5 to 125.0 seconds in steps of 0.5 sec.
Factory Value = 10.0 sec.; Manual Reference: 3.13
Range: 4 to 12 × FLC or OFF, in steps of 1 × FLC
Factory Value = OFF; Manual Reference: 3.16
Range: INST (instantaneous) or 0.5 to 20.5 seconds
in steps of 0.5 sec.
Factory Value = INST; Manual Reference: 3.16
269Plus Motor Management Relay
SETPOINTS MODE
3
3-
19