Mpm Option Specifications - GE 269Plus Instruction Manual

Motor management relay
Table of Contents

Advertisement

1 INTRODUCTION
PHASE CURRENT INPUTS
Conversion:
true rms, 64 samples/cycle
CT input:
1A and 5A secondary
Burden:
0.2 VA
Overload:
20 x CT for 1 s,
100 x CT for 0.2 s
Range:
1 to 150% of CT primary
Frequency:
up to 32
Accuracy:
±1% of display
VOLTAGE INPUTS
Conversion:
true rms, 64 samples/cycle
VT pri/Sec:
direct or 120 to 72000:69 to 240
Input range:
20 to 600 V AC
Full scale:
150/600 V AC autoscaled
Frequency:
up to 32
Accuracy:
±1% of display
ANALOG OUTPUTS
0 - 1 m A ( T 1 O p t i o n )
M A X L O A D
2 4 0 0
M A X O U T P U T
1 . 1 m A
Accuracy:
±2% of full scale reading
Isolation:
50 V isolated, activesource
MEASURED VALUES
PARAMETER
ACCURACY
% O F F U L L S C A L E
VOLTAGE
±0.2%
kW
±0.4%
kVar
±0.4%
kVA
±0.4%
kWh
±0.4%
PF
±1.0%
FREQUENCY
±0.02 Hz
CONTROL POWER
Input:
90 to 300 V DC or
70 to 265 V AC, 50/60 Hz
Power:
nominal
maximum 20 VA
Holdup:
100 ms typical
(@ 120 V AC/125 V DC)
GE Power Management
Courtesy of NationalSwitchgear.com
nd
harmonic
nd
harmonic
O U T P U T
4 - 2 0 m A ( T 2 0 O p t i o n )
6 0 0
2 1 m A
RANGE
20% to 100% of VT
0 to 999,999.99 kW
0 to 999,999.99 kvar
0 to 999,999.99 kVA
0 to 999,999,999 kWh
±0.00 to 1.00
20.00 to 70.00 Hz
10 VA
269Plus Motor Management Relay

MPM OPTION SPECIFICATIONS

1.6 MPM OPTION SPECIFICATIONS
TYPE TESTS
Dielectric strength:
2.0 kV for 1 minute to relays, CTs,
VTs, power supply
Insulation resistance: IEC255-5, 500 V DC
Transients:
ANSI C37.90.1 Oscillatory 2.5 kV/
1MHz
ANSI C37.90.1 Fast Rise 5 kV/10 ns
Ontario Hydro A-28M-82
IEC255-4 Impulse/High
Frequency Disturbance
Class III Level
Impulse test:
IEC 255-5 0.5 Joule 5 kV
RFI:
50 MHz/15 W Transmitter
EMI:
C37.90.2 Electromagnetic Interfer-
ence @ 150 MHz and 450 MHz,
10V/m
Static:
IEC 801-2 Static Discharge
Humidity:
95% non-condensing
Temperature:
–10°C to +60°C ambient
Environment:
IEC 68-2-38 Temperature/Humidity
Cycle
Dust/moisture:
NEMA 12/IP53
PACKAGING
Shipping box:
8½" × 6" × 6" (L × H × D)
215 cm × 152 cm × 152 cm
(L × H × D)
Ship weight:
5 lbs/2.3 kg
CERTIFICATION
ISO:
Manufactured to an ISO9001 certi-
fied program
UL:
Recognized under E83849
CSA:
Recognized under LR41286
It is recommended that all relays be pow-
ered up at least once per year to avoid
deterioration of electrolytic capacitors in
NOTE
the power supply.
Due to updating technology, specifications may
be improved without notice.
1
1-
9

Advertisement

Table of Contents
loading