1 INTRODUCTION
RELAY CONTACTS
VOLTAGE
RESISTIVE
30 VDC
125 VDC
250 VDC
INDUCTIVE
30 VDC
(L/R=7ms)
125 VDC
250 VDC
RESISTIVE
120 VAC
250 VAC
INDUCTIVE
120 VAC
PF=0.4
250 VAC
configuration
FORM C NO/NC
contact material
silver alloy
minimum permissible
load:
5 V DC, 100 mA
12 V AC, 100 mA
SWITCH INPUTS
Type:
Dry contacts
DO NOT CONNECT LIVE CIRCUITS TO THE DIGI-
TAL SWITCH INPUTS. THEY ARE DESIGNED FOR
DRY CONTACTS ONLY!
CAUTION
CT BURDEN DUE TO CONNECTION OF RELAY
CT INPUT
(AMPS)
PHASE
1
CT
4
(1A)
13
PHASE
5
CT
20
(5A)
65
G/F CT
5
(5A)
10
G/F CT
0.025
(50:0.025)
0.1
0.5
GE Power Management
Courtesy of NationalSwitchgear.com
MAKE/CARRY
MAKE/
BREAK
CONTINUOUS
CARRY 0.2s
10
30
10
30
10
30
10
30
10
30
0.25
10
30
0.15
10
30
10
30
10
30
10
30
BURDEN
(mΩ Ω Ω Ω )
(VA)
0.04
43
0.5
31
4.8
28
0.06
2.4
1
2.5
8.5
2.01
0.08
3
0.3
3
696 Ω
0.435
329 Ω
3.29
200 Ω
50
269Plus Motor Management Relay
CT THERMAL WITHSTAND
Phase CT (1A, 5A) & G/F 5A tap:
10
Phase CT 1A & 5A:
0.5
0.3
G/F 50:0.025 mA:
5
CONTROL POWER (INCLUDES TOLERANCES)
Frequency:
LO range:
10
HI range:
10
4
Max. power consumption:
3
Voltage low ride-through time: 100 ms
Relay can be powered from either AC or DC
source. If Control Power input exceeds 250 V, an
external 3 A fuse must be used rated to the
NOTE
required voltage.
INTERNAL FUSE SPECIFICATIONS
T3.15A H 250 V
Timelag high breaking capacity
DIELECTRIC STRENGTH ROUTINE TEST
2200 V AC, 50/60 Hz for 1 sec.
GROUND (Terminal 42) to
Output Contacts (Terminals 29 through 40)
Control Power (Terminals 41 & 43)
Current Transformer Inputs (Terminals 72
through 83)
If Hi-Pot tests are performed, jumper J201
beside Terminal 43 should be placed in the "HI-
POT" position. Upon completion of Hi-Pot
NOTE
tests, the jumper should be placed in the
"GND" position. See Figure 5–3: HI-POT TEST-
ING on page 5–6.
To avoid electrical shock, discharge J201 by
shorting across the pins before reconnecting
the J201 jumper.
WARNING
TECHNICAL SPECIFICATIONS
3 ×: continuous
6 ×: 40 sec.
12 ×: 3 sec.
40 x: 2 sec.
80 x: 1 sec.
6 ×: continuous
50/60 Hz
20 to 60 V DC
20 to 48 V AC
90 to 300 V DC
80 to 265 V AC
20 VA
(at 120 V AC/125 V DC)
1
1-