EXCLUSIVE
- select LPG
SERVICE
The boiler DOES NOT requires additional adjustments.
b
The boiler may only be converted by qualified staff.
b
After conversion apply the new rating plate contained in the kit.

5.13 Combustion check

To carry out the combustion analysis, proceed as follows:
- power the boiler electrically by setting the main system switch to "ON"
- set the status of the boiler to OFF
- access the technical parameters as explained in the section "4.1 Access
to the technical parameters"
- select SWEEPER with the "up" and "down" keys, confirming the
selection
INSTALLER
select ACTIVATE FUNCTION with the "up" and "down" keys, confirming
-
the selection.
PWM
blu (-)
3
P
X8
marrone (+)
1
230 V
OPE
OPE
ausiliario
M4
1
2
3
4
blu
blu
marrone
marrone
1
2
3
4
5
INSTALLER
rosa
- Note: the sweeper function can also be activated by pressing the
SW1 key on the electronic board AKM01 (this requires removing the
5
4
3
2
1
6
plug (C) from the cover of the instrument panel to access the electrical
components).
X1
X1
X15
X4
6
1
2
1
5
1
F2=4A T
1
AKM0x
6
1
5
1
1
10
12
X25
X9
X19
20
F.L.
GAS TYPE
NG
LPG
TECHNICAL
PARAMETERS
THERMOREGULATION
RANGE RATED
CALIBRATION
SWEEPER
SWEEPER
230 V
V Hv
N L
F= 3.15A F
ACTIVATE FUNCTION
M3
F
2
1
X15
arancione
combustion analysis button SW1
E.R.
X6
X3
X7
3
1
SW1
4
3
1
5
1
4
1
6
1
1
X13
X8
X21
X2
X16
T.P.
Wait for the burner to ignite.
The boiler will operate at maximum heating output and it will be possible to
regulate the combustion.
- Insert the analyser probes in the specific positions on the air distribution
box, after removing screw (A) and cap of the flue gases analysis socket (B).
- Perform the combustion check verifying that the CO
to those indicated in the multigas table.
- Once checking completed, remove the analyser probe and close the
combustion analysis sockets with appropriate caps and screw.
b
If the value displayed is different DO NOT OPERATE ANY
ADJUSTMENT ON THE GAS VALVE, please contact the Technical
Assistance Centre.
b
The gas valve DOES NOT requires adjustments and the possible
tampering causes a malfunction or failure of the boiler.
b
When the sweeper function is in progress all the heat requests are
inhibited and a scrolling message appears at the foot of the main
page of the REC10; green and red LEDs are off.
When the checks are completed:
- set the boiler to "SUMMER" or "WINTER" mode depending on the season
- regulate the heat request temperature values according to the customer's
needs.
IMPORTANT
The sweeper function is active for a time limit of 15 minutes; the burner
shuts down if an outlet temperature of 95° C is reached. It will ignite again
when the temperature falls below 75° C.
b
In case of a low temperature system we recommend carrying out
the efficiency test by taking hot water setting the boiler STATE to
SUMMER, opening the hot water tap to full capacity and setting the
temperature of the domestic hot water to the maximum.
b
All controls must be carried out exclusively by the Technical
Assistance Centre.
5.14 Range rated
C.S.A.
This boiler can be adapted to the system thermal requirements as it is
possible to set the maximum flow rate for the boiler operation in heating
mode:
- power on the boiler
- access the parameters as explained in paragraph "4.1 Access to the
technical parameters"
- select RANGE RATED and confirm it
5
4
3
2
1
X4
6
- set the desired heating maximum value (rpm) with the "up" and "down"
keys, confirming the selection
1
5
1
A
TSC2
N
F
EA
3
2
1
TECHNICAL
X6
INSTALLATION
PARAMETERS
THERMOREGULATION
BE20
RANGE RATED
1
2 3
4
J1
CALIBRATION
INSTALLER
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
1
2 3
4
X10
- A B +
values correspond
2
B
REC
1 2
5 6
7 8
9 10
1415 16 17
(RT)
(TBT)
(ES)
+
B
A
-
(OT+)
OT+ SBOL X
TA TBOL TBT SE
Utilizzare contatto privo di te

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents