4. Installation
L =
+
L =
+
L =
+
34
n Room sealed flue (C33, C63, C93)
If using a room sealed version, it is necessary to connect both the
combustion gas exhaust and the air-supply opening (parallel). For the
application of air discharge and combustion gas discharge piping with
a diameter other than 250 mm, an adapter should be used.
R000358-A
R000362-A
n (C53, C83) connection
Combustion air supply and combustion gas discharge are possible in
various pressure zones, semi-CLV systems. With the exception of
coastal areas. The maximum permissible difference in height
between the combustion air supply and the combustion gas discharge
is 36 m.
R000359-A
C 330 ECO Chimney length for room sealed operation
Boiler type
with a Ø of 200 mm with a Ø of 250 mm with a Ø of 300 mm
280
42 m
350
21 m
430
13 m
500
10 m
570
5 m
650
4 m
(1) Calculated with rigid pipe and Outlet without hood (open 'free')
C 630 ECO Chimney length for room sealed operation
Boiler type
with a Ø of 300 mm with a Ø of 350 mm with a Ø of 400 mm
560
50 m
700
43 m
860
26 m
1000
13 m
1140
5 m
1300
5 m
(1) Calculated with rigid pipe and Parallel roof feed-through 350 mm (Accessory)
C 330 ECO
Chimney length in the various pressure zones
Boiler type
280
350
430
500
570
650
(1) Calculated with rigid pipe and Elbow 90º and Outlet without hood (open 'free')
C 330 ECO - C 630 ECO
(1)
Maximum length (L)
50 m
50 m
50 m
50 m
34 m
30 m
(1)
Maximum length (L)
50 m
50 m
50 m
35 m
16 m
18 m
(1)
Maximum length (L)
with a Ø of 250 mm
50 m
50 m
50 m
50 m
49 m
40 m
31/05/2012 - 7600532-01
50 m
50 m
50 m
50 m
50 m
50 m
50 m
50 m
50 m
50 m
24 m
28 m