5.4.2 Entering the Motor Data

SIEMENS
3RW44
Menu
ESC
OK
Display mea-
1
1
sured value
select
select
ESC
OK
Status
2
display
select
ESC
OK
3
Settings
select
ESC
OK
OK
1
Parameter
set 1
select
OK
ESC
Motor 1
Adjustable
from ... to
ESC
0 ... I
Rated operating
e
(3RW44 device
current Ie
name plate)
Rated operating
torque
0 ... 10,000 Nm
Rated operating
speed
-1
500 ... 3,600 min
Function call
Copy motor data
to PS2+3
Copy motor data
to PS2+3
ESC
Figure 5-6: Entering the motor data and name plate
Rated operating
current I
e
SIRIUS 3RW44 manual
GWA 4NEB 535 2195-02 DS 06
1
select
OK
1
40.5 A
change
ESC
OK
2
143 Nm
change
ESC
OK
3
1470
change
ESC
OK
OK
ESC
OK
execute?
OK
OK
Notice
Always set the rated operating current of the motor stated on the motor name plate based
on the prevailing line voltage. This setting is independent of the type of connection of the
soft starter (soft starter in standard or inside delta circuit). Value to be set in the above
example for a line voltage of 400 V, e.g. 40.5 A.
The motor current of the connected drive should be set to ensure proper functioning of the
soft starter during starting and stopping, as well as in regard to motor protection.
Commissioning
5-11