Commissioning
5.2

Switching on for the First Time

5.2.1 Recommendation on Procedure for 3RW44 Commissioning

Suggested setting
Starting mode: Voltage ramp and current limiting
Start
voltage
%
Application
Conveyor belts
70
Powered roller
60
conveyors
Compressors
50
Small ventilators
30
Pumps
30
Hydraulic pumps
30
Stirrers
30
Centrifugal machines 30
Milling machines
30
Large fans
30
Mills
50
Crushers
50
Circular saws/ribbon
30
saws
5-4
Warning
Before switching the device on for the first time, verify that the main/control
side is wired properly. Make sure that the line and control voltage comply with
the device-specific requirements (Chapter 10.3 "Technical Data").
Starting parameters
(U+current limiting)
Current
Starting
limiting
time s
value
10
deactivated deactivated (0 ms)
10
deactivated deactivated (0 ms)
4 x I
10
e
4 x I
10
e
4 x I
10
e
4 x I
10
e
4 x I
30
e
4 x I
30
e
4 x I
30
e
4 x I
60
e
4 x I
60
e
4 x I
60
e
4 x I
60
e
Notice
This table provides example set values. They are intended informational purposes only
and are non-binding. The set values depend on the particular application and must be
optimized during commissioning.
Stopping mode
Breakaway pulse
Torque control
Torque control
deactivated (0 ms)
Coasting down
deactivated (0 ms)
Coasting down
deactivated (0 ms)
Pump stop
deactivated (0 ms)
Coasting down
deactivated (0 ms)
Coasting down
deactivated (0 ms)
Coasting down
deactivated (0 ms)
Coasting down
deactivated (0 ms)
Coasting down
80 % / 300 ms
Coasting down
80 % / 300 ms
Coasting down
deactivated (0 ms)
Coasting down
Stopping parameters
Parameter
Stopping
Stopping
torque
time s
%
10
10
10
10
X
X
X
X
10
10
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
SIRIUS 3RW44 manual
GWA 4NEB 535 2195-02 DS 06