10.3.7 Branch Component Layout (Standard Circuit)

Standard circuit fuseless design
Soft starters
Nominal current
ToC
1
Q11
Type
A
2
Utilization class 1
): 3RW44 22 ... 3RW44 27: I
3RW44 22
29
3RW44 23
36
3RW44 24
47
3RW44 25
57
3RW44 26
77
3RW44 27
93
3RW44 34
113
3RW44 35
134
3RW44 36
162
3RW44 43
203
3RW44 44
250
3RW44 45
313
3RW44 46
356
3RW44 47
432
3RW44 53
551
3RW44 54
615
3RW44 55
693
3RW44 56
780
3RW44 57
880
3RW44 58
970
3RW44 65
1076
3RW44 66
1214
1) The rated motor current must be taken into consideration during device selection.
2) For utilization class, see page 10-20.
SIRIUS 3RW44 manual
GWA 4NEB 535 2195-02 DS 06
Fuse assignment
The utilization class according to which the motor branch with soft starter is
dimensioned depends on the requirements of the application. Normally, a fuseless
design (combination of circuit breaker + soft starter) is sufficient. If the requirements
for utilization class 2 must be met, semiconductor fuses must be used in the motor
branch.
Q1
Q11
M
3~
1)
Circuit breaker
440 V +10 %
Rated current
Q1
Type
A
= 32 kA; 3RW44 34 and 3RW44 35: I
q
3RV10 42-4HA10
50
3RV10 42-4JA10
63
3RV10 42-4KA10
75
3RV10 42-4LA10
90
3RV10 42-4MA10
100
3RV10 42-4MA10
100
3VL17 16-2DD36
160
3VL17 16-2DD36
160
3VL37 25-2DC36
250
3VL47 31-3DC36
315
3VL47 31-3DC36
315
3VL47 40-3DC36
400
3VL47 40-3DC36
400
3VL57 50-3DC36
500
3VL67 80-3AB36
800
3VL67 80-3AB36
800
3VL67 80-3AB36
800
3VL77 10-3AB36
1000
3VL77 10-3AB36
1000
3VL77 12-3AB36
1250
3VL77 12-3AB36
1250
3VL77 12-3AB36
1250
= 16 kA; 3RW44 36 ... 3RW44 66: I
q
q
General Technical Data
= 65 kA