8.12.3 Data Set 72 - Log List - Reading Device Errors

SIRIUS 3RW44 manual
GWA 4NEB 535 2195-02 DS 06
Byte
Meaning
0 - 3
Operating hours - device
4 - 5
ID number of the device
error
6 - 9
Operating hours - device
10 - 11
ID number of the device
error
etc.
120 - 123 Operating hours - device
124 - 125 ID number of the tripping
Table 8-19: Data set 72 - log list - reading device errors
This data set can record 21 entries. When all spaces are filled, the first entry is
overwritten.
Note
The latest entry is entered at the end of the data set. The remaining entries are
moved up by one entry.
The following messages can be entered:
ID No.
452
Heatsink - thermistor defective
1466
Switching element 1 failed
1467
Switching element 2 failed
1468
Switching element 3 failed
1417
Bypass element fault
PROFIBUS DP Communication Module
Value range
32
1 ... 2
s
0 ... ± 32,767
32
1 ... 2
s
0 ... ± 32,767
32
1 ... 2
s
0 ... ± 32,767
Device error - Messages
Increment
Comment
1 second
Oldest
entry
1
1 second
Second oldest
entry
1
1 second
Last,
newest entry
1
8-43