Data Set 96 - Reading The Maximum Pointer - Siemens SIRIUS 3RW44 User Manual

Soft starter
Hide thumbs Also See for SIRIUS 3RW44:
Table of Contents

Advertisement

PROFIBUS DP Communication Module

8.12.13 Data Set 96 - Reading the Maximum Pointer

ID
Bit
Byte
No.
Maximum pointer
656
4
Phase current I
657
5
Phase current I
658
6
Phase current I
7
Reserved = 0
653
8
Phase current I
654
9
Phase current I
655
10
Phase current I
11
Reserved = 0
652
12
Maximum
tripping current I
651
14
Number of motor overload
trips
659
16
Maximum
tripping current I
660
20
Phase current I
661
24
Phase current I
662
28
Phase current I
663
32
Phase current I
664
36
Phase current I
665
40
Phase current I
666
44
Phase-to-phase voltage
U
L1 - L2min
667
46
Phase-to-phase voltage
U
L2 - L3min
668
48
Phase-to-phase voltage
U
L3 - L1min
669
50
Phase-to-phase voltage
U
L1 - L2max
670
52
Phase-to-phase voltage
U
L2 - L3max
671
54
Phase-to-phase voltage
U
L3 - L1max
672
56
Electronics supply voltage
U
NS min
8-58
Meaning
(%)
0 ... 797 % / [0 ... 255]
L1 min
(%)
0 ... 797 % / [0 ... 255]
L2 min
(%)
0 ... 797 % / [0 ... 255]
L3 min
(%)
0 ... 797 % / [0 ... 255]
L1 max
(%)
0 ... 797 % / [0 ... 255]
L2 max
(%)
0 ... 797 % / [0 ... 255]
L3 max
0 ... 1, 000 % /
(%)
[0 ... 320]
A max
0 ... 65, 535 /
[0 ... 65, 535]
0 ... 20 ,000 A /
(rms)
[0 ... 2 ,000 ,000]
A max
(rms)
0 ... 20, 000 A /
L1 min
[0 ... 2 ,000, 000]
(rms)
0 ... 20, 000 A /
L2 min
[0 ... 2 ,000 ,000]
(rms)
0 ... 20 ,000 A /
L3 min
[0 ... 2 ,000 ,000]
(rms)
0 ... 20, 000 A /
L1 max
[0 ... 2 ,000, 000]
(rms)
0 ... 20, 000 A /
L2 max
[0 ... 2 ,000 ,000]
(rms)
0 ... 20, 000 A /
L3 max
[0 ... 2 ,000 ,000]
0 ... 1 ,500 V /
(rms)
[0 ... 15 ,000]
0 ... 1,500 V /
(rms)
[0 ... 15,000]
0 ... 1 ,500 V /
(rms)
[0 ... 15, 000]
0 ... 1 ,500 V /
(rms)
[0 ... 15 ,000]
0 ... 1, 500 V /
(rms)
[0 ... 15, 000]
0 ... 1 ,500 V /
(rms)
[0 ... 15, 000]
0 ... 1 ,500 V /
(rms)
[0 ... 15, 000]
Value range / [coding]
Incre-
Comment
ment
3.125 %
In bypass operation
3.125 %
In bypass operation
3.125 %
In bypass operation
3.125 %
In bypass operation
3.125 %
In bypass operation
3.125 %
In bypass operation
3.125 %
Current during switch-off due
to error
1
Motor protection, temperature
sensor, stalling
0.01 A
Current during switch-off due
to error
0.01 A
In bypass operation
0.01 A
In bypass operation
0.01 A
In bypass operation
0.01 A
In bypass operation
0.01 A
In bypass operation
0.01 A
In bypass operation
0.1 V
0.1 V
0.1 V
Reset to 0 after loss of phase
or switch-off of the main
0.1 V
voltage.
0.1 V
0.1 V
0.1 V
Reset to zero during "Power
on".
SIRIUS 3RW44 manual
GWA 4NEB 535 2195-02 DS 06