Siemens SIRIUS 3RW44 User Manual page 136

Soft starter
Hide thumbs Also See for SIRIUS 3RW44:
Table of Contents

Advertisement

PROFIBUS DP Communication Module
8-12
5. In order to permanently save the settings, proceed as follows:
Station address
4
23
select
change
ESC
OK
Fieldbus
10
10
select
select
ESC
OK
Saving
11
options
select
execute
ESC
OK
Function call
Save
settings
select
execute
ESC
OK
Save
settings
execute?
ESC
Notice
If the parameter "Parameters disabled CPU/Master" is set to "Off" (factory setting) in the
menu "Field bus", the parameters set on the soft starter will be overwritten with the values
stored in the GSD data or in the OM when the bus is started. If this is not desired, the
parameter must be set to "On".
1
1
select
Yes
OK
SIEMENS
3RW44
Menu
ESC
OK
SIRIUS 3RW44 manual
GWA 4NEB 535 2195-02 DS 06

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents