Commissioning
"Voltage ramp" starting mode
SIEMENS
3RW44
Menu
ESC
OK
Display mea-
1
1
sured value
select
select
ESC
OK
2
Status
display
select
ESC
OK
3
Settings
select
OK
ESC
OK
1
Parameter
set 1
select
OK
ESC
Motor 1
ESC
Starting
settings
ESC
Starting mode
Adjustable
from ... to
Voltage ramp
ESC
Start voltage
20 ... 100 %
ESC
Starting time
0 ... 360 s
ESC
Maximum
starting time
1 ... 1,000 s
deactivated
ESC
Breakaway
40 ... 100 %
voltage
ESC
Breakaway time
0 ... 2,000 ms
ESC
Figure 5-8: "Voltage ramp" starting mode
5-14
Voltage in %
U
100 %
Motor
Breakaway voltage
Start voltage
4_1_Menü_Startart_Spannungsrampe.wmf
1
select
OK
2
select
OK
OK
1
change
OK
2
40.0 %
change
OK
5
20 s
change
OK
6
change
OK
8
80 %
change
OK
9
0 ms
change
OK
Breakaway time
starting time
Maximum starting time
100 % Voltage
at the motor
SIRIUS 3RW44 manual
GWA 4NEB 535 2195-02 DS 06
Time (t)