8.10

Data Formats and Data Sets

8.10.1 Characteristics

Control data
Messages
Diagnosis
Current values
SIRIUS 3RW44 manual
GWA 4NEB 535 2195-02 DS 06
The soft starter acquires a multitude of operating, diagnostics and statistics data.
Data transmitted to the soft starter, e.g. Motor LEFT switching command, Trip
reset, etc.
Data format: Bit
Data transmitted by the soft starter indicating the current operating status, e.g.
Motor left, etc.
Data format: Bit
Data transmitted by the soft starter indicating the current operating status, e.g.
Overload fault mode, etc.
Data format: Bit
Current values are coded in different current formats, in
• 6-bit current format,
• 8-bit current format and
• 9-bit current format:
9-bit current format
8-bit current format
6-bit current format
Bit
8
7
6
5
3
2
1
0
2
2
2
2
2
1 + 0.5 + 0.25 + 0.125 + 0.0625 + 0.03125 = 1.96875 (q 0 to 197 %)
4 + 2
1 + 0.5 + 0.25 + 0.125 + 0.0625 + 0.03125 = 7.97 (q 0 to 797 %)
8 + 4 + 2
1 + 0.5 + 0.25 + 0.125 + 0.0625 + 0.03125 = 15.97 (q 0 to 1597 %)
Figure 8-8: Current formats
Current values are
• Motor current I
(6-bit current format)
max
• Phase currents I
L1max
• Last trigger current (9-bit current format)
• Maximum tripping current (9-bit current format)
PROFIBUS DP Communication Module
4
3
2
1
0
-1
-2
-3
-4
-5
2
2
2
2
, I
, I
(8-bit current format)
L2max
L3max
8-35