iCON100/iCON100-SR QUICK INSTALLATION GUIDE
4.1.2 Recommended Cable Type and Permissible Length of Cable
Reference
Reader (Power and Data)
*
Extra Reader -> iCON100
* Requires thicker wire if you connect the reader with high current consumption.
Description
Power (DC12V)
DC Power -> iCON100
Door Contact
Exit Button
Sensor Input
Input -> iCON100
Door Lock, Alarm Device
Lock (Alarm) -> iCON100
RS232 Cable
Converter -> Host P.C.
RS485 Cable
iCON100 -> iCON100
iCON100 -> Converter
RS422 Cable
iCON100 -> iCON100
iCON100 -> Converter
Cable Specification
Belden #9409, 18 AWG
2 conductor, unshielded
Belden #9512, 22 AWG
4 conductor, shielded
Belden #9514, 22 AWG
8 conductor, shielded
Belden #9512, 22 AWG
4 conductor, shielded
Belden #9514, 22 AWG
8 conductor, shielded
Belden #9409, 18AWG
2 conductor, unshielded
Belden #9829, 24 AWG
2-twisted pair, shielded
Belden #9829, 24 AWG
2-twisted pair, shielded
Belden #9830, 24 AWG
3-twisted pair, shielded
7
Maximum
Distance
3m
150m
300m
300m
15m
1,200m

Advertisement