5.2 I Error code display

Display of
Air temperature sensor fault
Deicing sensor fault
Low-pressure fault
High-pressure fault
Water temperature sensor
fault
Deicing cycle fault (>20
minutes)
13
Possible causes
SD2 sensor is offl ine or incorrectly
connected
SD3 sensor is offl ine or incorrectly
connected
Low pressure fault in the cooling
circuit (if fault persists aft er
acknowledgement)
Air and water emulsion passed
into the device
Insuffi cient water fl ow
Water temperature too high
(32°C maximum)
Flow controller blocked
Water condenser scaled up or
blocked
SD1 sensor is offl ine or incorrectly
connected
Air temperature too low
The evaporator is scaled up
The venti lator does not work
Wrong value provided by the air
or deicing sensor
Soluti ons
Sensor replacement
Sensor replacement
Call an approved technician
Check the pool's hydraulic circuit
Increase fl ow using by-pass,
check that the pool fi lter is not clogged
Wait unti l the temperature falls
Check the fl ow controller
Clean the water condenser
Sensor replacement
Wait unti l the temperature is
within the operati ng range
Clean the evaporator (see § "4.2 I
Maintenance")
Replace the venti lator or the electronic
board
Replace the sensor.