4.2 I Error code display

Display
Error 01
Communication
fault between the
regulation board
and the display
board
Error 02
Overheating on the
electronic board
Error 03
Automatic
protection against
electrical network
instabilities
Error 05
Error on the
ventilator motor
Error 06
Compressor supply
overheating
Error 07
Compressor supply
overintensity
Error 08
Low pressure fault
on cooling circuit
Error 09
Cooling circuit high
pressure fault
Error 10
ST3 sensor fault
Defrost sensor
Error 11
ST sensor fault air
intake sensor
13
Possible causes
Bad connection between the A1
and A2 boards
Board power supply fault
Faulty boards
Machine's rear panel slots
blocked
Ventilator operating incorrectly
Electrical network overvoltage
or interruption or drop in the
network voltage
Incorrect earthing
A1 board operating incorrectly
Ventilator motor disconnected
Ventilator motor damaged
Machine's rear panel slots
blocked
Ventilator operating incorrectly
Electrical supply over or
undervoltage
Compressor operating incorrectly
A1 board operating incorrectly
Incorrect connection of the
masses to the earth.
Pressure fault in the low pressure
circuit (if problem persists after
resetting)
Exchanger clogged with dirt
Insufficient water flow
Air and water emulsion passed
into the device
Flow controller blocked
Sensor is faulty or offline (J14
connector)
Sensor is faulty or offline (J12
connector)
Solutions
Check the RJ11 and RJ45
connectors on the link cable between
the boards
Check the boards' power supply
Replace the boards
Clean the rear panel If problem
persists, call an approved technician
Replace the ventilator motor
Check the quality of the electrical
network
Check that the eart cables are
correctly connected
Replace the A1 board
Check the ventilator motor
connector. If problem persists, call an
approved technician
Replace the ventilator motor
Clean the rear panel
If problem persists, call an approved
technician
Replace the ventilator motor
Check the electrical supply
voltage (maximum 240V ±10%)
Replace the compressor
Replace the A1 board
Check that the eart cables are
correctly connected
Call an approved technician
Clean the water exchanger
Increase flow using by-pass, check
that the pool filter is not clogged
Check the pool's hydraulic circuit
Check the flow controller
Reconnect or change the sensor
Reconnect or change the sensor
Resetting
Automatic (if fewer
than 4 faults per
hour) or press
Automatic
Automatic (if fewer
than 4 faults per
hour) or press
Automatic (if fewer
than 4 faults per
hour) or press
Automatic (if fewer
than 4 faults per
hour) or press
Automatic (if fewer
than 4 faults per
hour) or press
Automatic (if fewer
than 4 faults per
hour) or press
Automatic (if fewer
than 4 faults per
hour) or press
Automatic (if fewer
than 4 faults per
hour) or press
Press
Press