Functionality - ABB REG670 Technical Manual

Relion 670 series 2.0 iec generator protection
Hide thumbs Also See for REG670:
Table of Contents

Advertisement

Section 21
IED hardware
21.2.16.3
1194
I/O
100k W
100nF
Soft ground
en07000242.vsd
IEC07000242 V1 EN
Figure 544:
Schematic view of soft earth
Earthing
Three different kinds of earthing principles can be set (used for fault tracing):
1.
Direct earth - The normal earthing is direct earth, connect terminal 2 directly to
the chassis.
2.
No earth - Leave the connector without any connection.
3.
Soft earth - Connect soft earth pin (3), see figure
X.21 connector
Table 924:
Pinout for the X.21 communication connector
Pin number
Signal
1
Shield (earth)
2
TXD A
3
Control A
4
RXD A
6
Signal timing A
8
Earth
9
TXD B
10
Control B
11
RXD B
13
Signal timing B
5,7,12,14,15
Not used

Functionality

The data format is HDLC. The speed for the transmission of the messages used is 64
kbit/s.
1MRK502052-UEN B
543
Technical manual