ABB REG670 Technical Manual page 1263

Relion 670 series 2.0 iec generator protection
Hide thumbs Also See for REG670:
Table of Contents

Advertisement

1MRK502052-UEN B
Technical manual
Table 964:
RI and RD type inverse time characteristics for Line Differential protection
Function
RI type inverse characteristic
1
=
×
t
k
0.236
-
0.339
I
EQUATION1137-SMALL V1 EN
I = I
/I
measured
set
RD type logarithmic inverse characteristic
æ
ö
I
-
ç
×
÷
5.8
1.35
In
=
t
è
ø
k
EQUATION1138-SMALL V1 EN
I = I
/I
measured
set
Table 965:
ANSI Inverse time characteristics for Sensitive directional residual overcurrent and
power protection
Function
Operating characteristic:
æ
ö
A
ç
÷
=
+
× +
t
B k tDef
(
)
ç
÷
P
ç
-
÷
I
1
è
ø
EQUATION1249-SMALL V2 EN
Reset characteristic:
t r
=
×
t
k
(
)
2
-
I
1
EQUATION1250-SMALL V1 EN
I = I
/I
measured
set
ANSI Extremely Inverse
ANSI Very inverse
ANSI Normal Inverse
ANSI Moderately Inverse
ANSI Long Time Extremely Inverse
ANSI Long Time Very Inverse
ANSI Long Time Inverse
Inverse time characteristics
Range or value
k = (0.05-2.00) in steps of 0.01
k = (0.05-999) in steps of 0.01
Range or value
0.10 ≤ k ≤ 2.00
1.5 x I
≤ I ≤ 20 x I
set
set
A=28.2, B=0.1217, P=2.0 ,
tr=29.1
A=19.61, B=0.491, P=2.0 ,
tr=21.6
A=0.0086, B=0.0185, P=0.02,
tr=0.46
A=0.0515, B=0.1140, P=0.02,
tr=4.85
A=64.07, B=0.250, P=2.0,
tr=30
A=28.55, B=0.712, P=2.0,
tr=13.46
A=0.086, B=0.185, P=0.02,
tr=4.6
Section 25
Accuracy
IEC 60255-151, ± 5.0%
or ± 40 ms whichever is
greater
Accuracy
ANSI/IEEE C37.112 ,
±5.0% or ±160 ms
whichever is greater
1257

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents