Type Tests According To Standards - ABB REG670 Technical Manual

Relion 670 series 2.0 iec generator protection
Hide thumbs Also See for REG670:
Table of Contents

Advertisement

Section 22
Injection equipment hardware
22.5.2
1234
Table 951:
Degree of protection
Description
REX060
Front
Panel mounted, front
Rear, sides, top, bottom and connection terminals
REX061 and REX062
Top
Front, rear, sides and bottom

Type tests according to standards

Table 952:
Electromagnetic compatibility tests
Test
1 MHz burst disturbance
100 kHz slow damped
oscillatory wave immunity
test
Surge withstand capability
test
Electrostatic discharge
Direct application
Indirect application
Electrostatic discharge
Direct application
Indirect application
Fast transient disturbance
test
Surge immunity test
Power frequency immunity
test
Power frequency magnetic
field test
Radiated electromagnetic
field disturbance test
Radiated electromagnetic
field disturbance test
Conducted electromagnetic
field disturbance test
Voltage dips and short
interruptions
Radiated emission
Conducted emission
Values
IP40
IP54
IP20
IP41
IP20
Type test values
2.5 kV
2.5 kV
2.5 kV, oscillatory
4.0 kV, fast transient
15 kV air discharge
8 kV contact discharge
8 kV contact discharge
15 kV air discharge
8 kV contact discharge
8 kV contact discharge
4 kV
1-2 kV, and 2-4 kV, 1.2/50 µs
High energy
150-300 V, 50 Hz
1000 A/m, 3 s
100 A/m, cont.
20 V/m, 80-1000 MHz
1.4-2.7 GHz
20 V/m, 80-1000 MHz
10 V, 0.15-80 MHz
Dips:
40% /200 ms
70% /500 ms
Interruptions:
0-50 ms: No restart
0... ∞ s: Correct behaviour at
power down
30-1000 MHz
0.15-30 MHz
1MRK502052-UEN B
Reference standards
IEC 60255-26
IEC 61000-4-18, Class III
IEEE/ANSI C37.90.1
IEC 60255-26
IEC 61000-4-2, Class IV
IEEE/ANSI C37.90.3
IEC 60255-26, Zone A
IEC 60255-26, Zone A
IEC 60255-26, Zone A
IEC 61000-4-8
IEC 60255-26
IEEE/ANSI C37.90.2
IEC 60255-26
IEC 60255-26
IEC 60255-26
IEC 60255-26