Technical Data - ABB REG670 Technical Manual

Relion 670 series 2.0 iec generator protection
Hide thumbs Also See for REG670:
Table of Contents

Advertisement

1MRK502052-UEN B
21.2.10.6
Technical manual
Name
Type
BO12VALUE
BOOLEAN
BO12FORCE
BOOLEAN
BO12
BOOLEAN

Technical data

Table 911:
IOM - Binary input/output module
Quantity
Binary inputs
DC voltage, RL
Power consumption
24/30 V, 50 mA
48/60 V, 50 mA
110/125 V, 50 mA
220/250 V, 50 mA
220/250 V, 110 mA
Counter input frequency
Oscillating signal discriminator
Debounce filter
Maximum 176 binary input channels may be activated
simultaneously with influencing factors within nominal range.
Table 912:
IOM - Binary input/output module contact data (reference standard: IEC 61810-2)
Function or quantity
Binary outputs
Max system voltage
Test voltage across open contact,
1 min
Current carrying capacity
Per relay, continuous
Per relay, 1 s
Per process connector pin,
continuous
Table continues on next page
Values (Range)
Unit
1=1
-
0=0
0=Normal
-
1=Forced
0=Normal
-
1=Forced
2=Blocked
Rated value
8
24/30 V
48/60 V
110/125 V
220/250 V
max. 0.05 W/input
max. 0.1 W/input
max. 0.2 W/input
max. 0.4 W/input
max. 0.5 W/input
10 pulses/s max
Blocking settable 1-40 Hz
Release settable 1-30 Hz
Settable 1-20 ms
Trip and signal relays
10
250 V AC, DC
1000 V rms
8 A
10 A
12 A
Section 21
IED hardware
Description
Binary output 12 value
Binary output 12 force
Binary output 12 status
Nominal range
-
RL ±20%
RL ±20%
RL ±20%
RL ±20%
-
Fast signal relays (parallel reed
relay)
2
250 V DC
800 V DC
8 A
10 A
12 A
1179