Section 25
Inverse time characteristics
1260
Table 969:
IEC Inverse time characteristics for Voltage restrained time overcurrent protection
Function
Operating characteristic:
æ
ö
A
ç
÷
=
×
t
k
(
)
ç
÷
P
è
-
ø
I
1
EQUATION1251-SMALL V1 EN
I = I
/I
measured
set
IEC Normal Inverse
IEC Very inverse
IEC Inverse
IEC Extremely inverse
IEC Short time inverse
IEC Long time inverse
Table 970:
Inverse time characteristics for overvoltage protection
Function
Type A curve:
k
=
t
æ
ö
-
>
U
U
ç
÷
è
ø
>
U
EQUATION1436-SMALL V1 EN
U> = U
set
U = U
measured
Type B curve:
k
480
t
=
2.0
U
U
>
32
0.5
U
>
EQUATION1437-SMALL V2 EN
Type C curve:
k
480
t
=
3.0
U
U
>
32
0.5
U
>
EQUATION1438-SMALL V2 EN
Programmable curve:
×
k A
=
+
t
P
æ
ö
-
>
U
U
ç
×
-
÷
B
C
è
ø
>
U
EQUATION1439-SMALL V1 EN
Range or value
0.10 ≤ k ≤ 3.00
A=0.14, P=0.02
A=13.5, P=1.0
A=0.14, P=0.02
A=80.0, P=2.0
A=0.05, P=0.04
A=120, P=1.0
Range or value
k = (0.05-1.10) in
steps of 0.01
k = (0.05-1.10) in
steps of 0.01
+
0.035
k = (0.05-1.10) in
steps of 0.01
+
0.035
k = (0.05-1.10) in
steps of 0.01
A = (0.005-200.000)
in steps of 0.001
D
B = (0.50-100.00) in
steps of 0.01
C = (0.0-1.0) in steps
of 0.1
D = (0.000-60.000) in
steps of 0.001
P = (0.000-3.000) in
steps of 0.001
1MRK502052-UEN B
Accuracy
IEC 60255-151, ±5.0%
or ±40 ms whichever is
greater
Accuracy
±5.0% or ±45 ms
whichever is greater
Technical manual