ABB REG670 Technical Manual page 1224

Relion 670 series 2.0 iec generator protection
Hide thumbs Also See for REG670:
Table of Contents

Advertisement

Section 21
IED hardware
1218
Test
Pulse magnetic field
immunity test
Damped oscillatory magnetic
field test
Radiated electromagnetic
field disturbance
Radiated electromagnetic
field disturbance
Conducted electromagnetic
field disturbance
Radiated emission
Radiated emission
Conducted emission
Table 941:
Insulation
Test
Dielectric test
Impulse voltage test
Insulation resistance
Table 942:
Environmental tests
Test
Cold operation test
Cold storage test
Dry heat operation test
Dry heat storage test
Change of temperature test
Damp heat test, steady state
Damp heat test, cyclic
Table 943:
CE compliance
Test
Immunity
Emissivity
Low voltage directive
Type test values
1000 A/m
100 A/m
20 V/m, 80-1000 MHz
1.4-2.7 GHz
20 V/m
80-1000 MHz
10 V, 0.15-80 MHz
30-5000 MHz
30-5000 MHz
0.15-30 MHz
Type test values
2.0 kV AC, 1 min.
5 kV, 1.2/50 ms, 0.5 J
>100 MW at 500 VDC
Type test value
Test Ad for 16 h at -25°C
Test Ab for 16 h at -40°C
Test Bd for 16 h at +70°C
Test Bb for 16 h at +85°C
Test Nb for 5 cycles at -25°C
to +70°C
Test Ca for 10 days at +40°C
and humidity 93%
Test Db for 6 cycles at +25 to
+55°C and humidity 93 to
95% (1 cycle = 24 hours)
According to
EN 60255–26
EN 60255–26
EN 60255–27
1MRK502052-UEN B
Reference standards
IEC 61000–4–9, Class V
IEC 61000-4-10, Class V
IEC 60255-26
IEEE/ANSI C37.90.2
IEC 60255-26
IEC 60255-26
IEEE/ANSI C63.4, FCC
IEC 60255-26
Reference standard
IEC 60255-27
ANSI C37.90
Reference standard
IEC 60068-2-1
IEC 60068-2-1
IEC 60068-2-2
IEC 60068-2-2
IEC 60068-2-14
IEC 60068-2-78
IEC 60068-2-30