Type Tests According To Standard - ABB REG670 Technical Manual

Relion 670 series 2.0 iec generator protection
Hide thumbs Also See for REG670:
Table of Contents

Advertisement

1MRK502052-UEN B
21.5.5
Technical manual
Table 939:
Frequency influence (reference standard: IEC 60255–1)
Dependence on
Frequency dependence,
operate value
Frequency dependence
for distance protection
operate value
Harmonic frequency
dependence (20%
content)
Harmonic frequency
dependence for high
impedance differential
protection (10% content)
Harmonic frequency
dependence for high
impedance differential
protection (10% content)
Harmonic frequency
dependence for
overcurrent protection

Type tests according to standard

Table 940:
Electromagnetic compatibility
Test
1 MHz burst disturbance
100 kHz slow damped
oscillatory wave immunity
test
Ring wave immunity test, 100
kHz
Surge withstand capability
test
Electrostatic discharge
Direct application
Indirect application
Electrostatic discharge
Direct application
Indirect application
Fast transient disturbance
Surge immunity test
Power frequency immunity
test
Conducted common mode
immunity test
Power frequency magnetic
field test
Table continues on next page
Within nominal range
f
±2.5 Hz for 50 Hz
r
f
±3.0 Hz for 60 Hz
r
f
±2.5 Hz for 50 Hz
r
f
±3.0 Hz for 60 Hz
r
nd
rd
th
2
, 3
and 5
harmonic of f
th
2nd, 3rd and 5
harmonic of f
nd
th
2
, 3rd and 5
harmonic of f
nd
rd
th
2
, 3
and 5
harmonic of f
Type test values
2.5 kV
2.5 kV
2-4 kV
2.5 kV, oscillatory
4.0 kV, fast transient
15 kV air discharge
8 kV contact discharge
8 kV contact discharge
15 kV air discharge
8 kV contact discharge
8 kV contact discharge
4 kV
2-4 kV, 1.2/50 ms
high energy
150-300 V, 50 Hz
15 Hz-150 kHz
1000 A/m, 3 s
100 A/m, cont.
Section 21
IED hardware
Influence
±1.0% / Hz
±2.0% / Hz
±2.0%
r
±5.0%
r
±10.0%
r
±3.0% / Hz
r
Reference standards
IEC 60255-26
IEC 61000-4-18, Class III
IEC 61000-4-12, Class IV
IEEE/ANSI C37.90.1
IEC 60255-26
IEC 61000-4-2, Class IV
IEEE/ANSI C37.90.1
IEC 60255-26, Zone A
IEC 60255-26, Zone A
IEC 60255-26, Zone A
IEC 61000-4-16, Class IV
IEC 61000-4-8, Class V