8.1 pCO5+ Technical Specifi cations
Dimensions
Plastic case
Built-in terminal
Physical specifi -
cations
Other characteristics
Power supply
Attention: the pCO5+ with built-in driver must be powered with alternating current and the secondary winding of the power supply transformer
(G0) must be earthed.
Terminal block
Cable section
CPU
Non-volatile memory
(FLASH)
Electrical speci-
Data memory (RAM)
fi cations
Buff er memory T
(EEPROM)
Parameter memory P
(EEPROM)
Working cycle duration
(medium complexity
applications)
Clock with battery
Buzzer
Battery
Software class and
structure
Voltage surge
immunity category
(IEC EN 61000-4-5)
The device is not designed to be hand-held when powered
pCO5plus +0300020EN rel. 1.2 - 07.11.2013
8.

TECHNICAL SPECIFICATIONS

SMALL
MEDIUM, LARGE, EXTRALARGE
BUILT-IN DRIVER
Mounting
Material
Flame retardancy
Temperature for the ball pressure test 125 °C
Creeping current resistance
Colour
PGD1 (132x64 pixel) with backlit keypad
Operating conditions
Storage conditions
Protection rating
Control pollution situation
Class of protection against electric
shocks
PTI of insulating materials
Period of electrical stress across
insulating parts
Type of action
Type of disconnection or
microswitching
Category of resistance to heat and
fi re
Ageing characteristics (operating
hours)
No. of automatic operating cycles
Rated impulse voltage
SMALL, MEDIUM, LARGE, EXTRALARGE: Use a dedicated, class 2, 50 VA safety isolating transformer
BUILT IN DRIVER: Use a dedicated, class II, 100 VA safety isolating transformer
SMALL
MEDIUM
LARGE
EXTRALARGE
BUILT-IN DRIVER
(BUILT-IN VALVE DRIVER)
With plug-in male/female connectors
min 0.5 mm
2
- max 2.5 mm
2
32 bit, 100 MHz
P+3**********: 5 MB (2 MB BIOS + 3 MB application program + 2MB memory log fi le)
P+5**********: 9 MB (2 MB BIOS + 7 MB application program + 4MB memory log fi le)
3.2 MB (1.76 MB BIOS + 1.44 MB application program)
13 kB
32 kB (not visible from pLAN)
0.2 s (typical)
Supplied, accuracy 100 ppm
Can be software-enabled only via built-in terminal
3 Vdc lithium button battery (24x3 mm), code CR2430
Class A
Category III
13 DIN modules 110 X 227,5 X 60 mm
18 DIN modules 110 X 315 X 60 mm
18 DIN modules 110 X 315 X 75 mm
Can be mounted on DIN rail in accordance with DIN 43880 and IEC EN 50022
Technopolymer
V2 (standard UL94) and 850 °C (standard IEC 60695)
≥ 250 V
White RAL 9016
P+(3, 5)*******0** (no built-in terminal): -40T70 °C, 90% RH non-condensing(*)
P+(3, 5)*******E** (with built-in terminal): -20T60 °C, 90% RH non-condensing
(*) with Ultracap module installed: -40T60°C
P+(3, 5)*******0** (no built-in terminal): -40T70 °C, 90% RH non-condensing
P+(3, 5)*******E**(with built-in terminal): -30T70 °C, 90% RH non-condensing
Models with USB port and/or Ultracap module: IP20 (front panel only)
Models without USB port and without Ultracap module: IP40 (front panel only)
2
to be integrated into Class I and/or II units (on versions without valve driver), and
Class I units (on versions with valve driver)
PCB: PTI 250 V; insulating material: PTI 175
long
1C; 1Y in SSR versions
microswitching
Category D (UL94-V2)
80.000
100.000 (EN 60730-1); 30.000 (UL60730)
2500V
Vac
P (Vac)
24 Vac (+10/-
15%), 50/60 Hz
45 VA
to be protected
by 2.5 A T
external fuse
90 VA
46
Vdc
P (Vdc)
28 to 36 Vdc
(-20/+10%) to be
30 W
protected by 2.5 A
T external fuse