Carel pCO5+ User Manual page 45

Programmable controller
Table of Contents

Advertisement

Slave
Display
Protocol active on
USB
terminal
pCO5+
(Device)
PST terminal
Local terminal or pLAN
Local terminal or pLAN
Local terminal or pLAN
pLAN
pLAN or CAREL Master
or CAREL Master 5
expansions
CAREL Master or CAREL
Master 5 expansions
CAREL Master or CAREL
Master 5 expansions
CAREL Master 5 expansions Can be activated only on one serial port; incompatible with PST terminal
CAREL Master
CAREL Slave
Modbus slave extended
with pCOweb
Modbus Slave
Modbus Master
Modbus Master - Benshaw Maximum two Benshaw devices (addresses 1 and 2).
x
WinLoad
PSTN
GSM
MP-Bus
Serial printer
Pendrive
Mbus master for th-Tune
nd
2
Modbus slave
extended on BMS2
NOTES
Incompatible with CAREL Master 5 expansions
With Local Terminal the pGD* works in pCOT emulation mode
Can be activated only on one serial port. CAREL Master 5 expansions: incompatible with PST terminal
Can be activated only on one serial port. CAREL Master 5 expansions: incompatible with PST terminal. If the
protocol is activated, other devices cannot be supervised on J23.
CAREL Master: can be activated either on BMS or Fieldbus serial port.
Can be activated either on pLAN or Fieldbus serial port. When activated on Fieldbus serial port, the protocol is
deactivated on connector J23.
Can be activated only on one serial port
Can be activated only on one serial port at a time, except for BMS and Fieldbus serial ports on which at can be
activated simultaneously. If active on pLAN serial port, protocols PSTN, GSM, Modbus Slave and CAREL Slave
cannot be used on BMS serial port.
Modbus slave extended only for pCOWEB serial card with FW version >= 1.4
If Modbus Slave is active then CAREL Slave can be activated only on another serial port. The second Modbus
extended on BMS2 (with 10000 integer variables) can work at the same time as the one activated on the other
ports.
Can be activated on two serial ports at the same time (provided they are diff erent and have separate management
lists) by selecting the second Modbus Master.
Can be activated only on one serial port; on Fieldbus serial from BIOS 4.00
Can be activated only on one serial port
Incompatible with PSTN protocol; if activated on BMS serial port, is incompatible with CAREL Slave set on pLAN
serial port.
Can be activated only on one serial port at a time.
Incompatible with PSTN protocol; if activated on BMS serial port, is incompatible with CAREL Slave set on pLAN
serial port
Maximum 8 devices
Can be activated only on one serial port
USB master and USB slave port cannot be used at the same time
Can be activated on pLAN or Fieldbus serial port, but not on both at the same time
Version for 2048D (coil), 5000A, 10000l (15000 registers)
45
ENG
pCO5plus +0300020EN rel. 1.2 - 07.11.2013