Connecting current-output pressure probes
For information on the maximum number of probes that can be
connected see the table at the beginning of this paragraph. For details
on the operating range see the data sheets supplied with the probes.
The controller can be connected to all CAREL SPK* series active pressure
probes or any commercially available pressure probes with 0 to 20 mA or
4 to 20 mA signals.
J1
J24
1
2
Key
Controller
Current-output pressure probe
1
terminals
+VDC
Wire 1 Power
U1
Wire 2 Signal
U2
Connecting 0 to 5 V ratiometric pressure probes
For information on the maximum number of probes that can be
connected see the table at the beginning of this paragraph. For details
on the operating range see the data sheets supplied with the probes.
The controller can be connected to all CAREL SPKT series active pressure
probes or any commercially available pressure probes with 0 to 5 V
ratiometric signals.
Important:
the ratiometric probes are powered by the controller through terminal
+5 VREF;
the ratiometric probes cannot be powered by an external source.
J1
Key
Controller terminals
+5 V
Power
REF
GND
Power reference
U1
Signal
pCO5plus +0300020EN rel. 1.2 - 07.11.2013
FieldBus card
B M S card
J2
J3
J4
2
1
1
2
Fig. 5.f
2
Brown
Wire 1 Power
Brown
White
-
Wire 2 Signal
White
FieldBus card
B M S card
J4
J24
J2
J3
Fig. 5.g
Description
Wire colour
Black
Green
White
Connecting active probes with 0 to 10 V output
For information on the maximum number of probes that can be
connected see the table at the beginning of this paragraph. For details
on the operating range see the data sheets supplied with the probes.
J1
J
Key
Controller terminals
GND
Reference
+VDC
Power
U1
Signal 1
U2
Signal 2
Max. number of connectable digital inputs
The controller allows the universal inputs/outputs to be confi gured as
non-optically isolated, voltage-free digital inputs. In any case, the inputs
must be connected to a voltage-free contact.
Max. number of digital inputs connectable
to universal inputs/outputs
Type of signal
- voltage-free
Digital
contacts
inputs (not
optically
- fast digital
inputs
isolated)
Important: The maximum current allowed on the digital input is
10 mA. Therefore the rating of the external contact must be at least
10 mA.
Connecting the ON/OFF inputs
There is no particular restriction on the maximum number of inputs that
can be connected. For details on the operating range see the Technical
Specifi cations table.
J1
J24
Key
Controller terminals
U4
Digital input 1
GND
U5
Digital input 2
GND
28
FieldBus card
B M S card
J4
J24
J2
J3
Fig. 5.h
0 to 10 V active probes
pCO5+
Medium/ Built-in
Small
Large
driver/ Extralarge
5
8
10
6
4
(max 2 su U1...U5,
max 2
(max 2 su U1...U5,
max 2 su U6...U8,
max 2 su U6..U8)
2 su U9...U10)
FieldBus card
B M S card
J4
J2
J3
Fig. 5.i
Description
J
Tab. 5.c
J5