Functional Layout - Carel pCO5+ User Manual

Programmable controller
Table of Contents

Advertisement

ENG

1.2 Functional layout

The fi gure below shows the functional layout of an air handling
unit. Damper actuators and valve actuators are fi eld devices that
communicate through Fieldbus 1 (ref. C). Fieldbus 2 (ref. E) is the medium
through which the serial probes communicate the values measured,
and through which the humidifi er control board and the fans exchange
data and receive setpoints from the controller. The built-in terminal and
the remote terminal, which communicate via pLAN (ref. A), are used for
installing the application program and for commissioning the system.
The PGD touchscreen terminal, intuitive and simple to use, can be used
while the unit is normally working to set switch-on and switch-off times,
to enter the main parameters, to perform other advanced functions of
the application program and to view any alarms triggered. In this case the
data is communicated through the BMS2 serial port (ref. D). The system
can be connected to a supervision system (Konnex®, LON®, BACnet™, etc.)
after installing the relative BMS1 expansion card (ref. B).
Terminal
Terminale
A
pLAN
J10
J1
MP-BUS card
Scheda MP-BUS
MP -BUS
BELIMO
Servo-control
Valvola di
valve
servocontrollo
Ref. Serial port/Connectors
A
pLAN/J10, J11
B
BMS 1 Serial Card
C
FieldBus 1 Serial Card
D
BMS 2 / J25*
Fieldbus 2/J26 (and J23 on Large and
E
Extralarge versions)
(*) available on P+5... models; not available on P+3... models; see par. 8.3.
pCO5plus +0300020EN rel. 1.2 - 07.11.2013
PGD touchscreen
Terminale PGD
terminal
touch screen
D
BMS2
J1 2
J11 pLAN
J25 BMS2 J26 FBus2
FieldB us car d
J4
J24
J2
J3
C
FieldBus 1
B A Cnet
t s
t a
s u
P1
+
GNX
BELIMO
Damper servo-
Servocontrollo
control
della serranda
Fig. 1.a
Connection to:
up to 3 terminals
up to 32 devices in a pLAN network (pCO controllers, EVD Evolution valve drivers, terminals)
a building automation system, after installing the relative BMS card (see par. 1.4)
sensors, actuators, etc., on a Fieldbus, after installing the relative card (see par. 1.5)
pGD Touch terminals, GPRS connection modules (built-in card)
sensors, actuators, etc., on a Fieldbus (built-in card)
Humidifi er control
Scheda controllo
umidificatori
board
Serial probes
Sonde seriali
E
FieldBus 2
J1 5
J1 6
J1 3
J1 4
4
3
2
1
J2 1
J22
J1 9
B M S card
J5
J6
J7
B
BMS 1
RS485 serial card
Scheda seriale RS485
Scheda interfaccia
BACnet
TM
RS485
MS/TP
R
4 S
5 8
P2
P3
RS485
BACnet™ RS485
interface card
TM
TM
Ethernet
/BACnet
Sch. interfaccia
interface card
Ethernet™ /BACnet™
LonWorks interface
Scheda interfaccia
card*
LonWorks®
8
Dispositivo
terze parti
Device
FAN
J1 8
J1 7
J23 FBus2
J20
J8