Connecting NTC, PTC temperature probes
For information on the maximum number of probes that can be
connected see the table at the beginning of this paragraph. For details
on the operating range see the Technical Specifi cations table.
FieldBus card
J1
J24
J2
Fig. 5.b
Key
Controller terminals NTC probe
1
2
GND
Wire 1
U1
Wire 2
GND
Wire 1
U2
Wire 2
GND
U4
GND
U5
Connecting PT500/PT1000 temperature probes
For information on the maximum number of probes that can be
connected see the table at the beginning of this paragraph. For
details on the operating range see the Technical Specifi cations table.
Important:
to ensure correct measurements from the probe each wire must be
connected to only one terminal.
the two probe wires have no polarity.
input: 24 V 50...60 Hz / 28...36 V
max. power: 45 VA/20 W
FieldBus card
J1
J24
J2
Key
Controller
PT500/PT1000 probe
terminals
1
2
GND
Wire 1
U4
Wire 2
GND
Wire 1
U5
Wire 2
B M S card
J4
J3
3
4
Wire 1
Wire 2
Wire 1
Wire 2
B M S card
J4
J3
Fig. 5.c
Connecting PT100 temperature probes
For information on the maximum number of probes that can be
connected see the table at the beginning of this paragraph. For details
on the operating range see the Technical Specifi cations table.
The probe has three wires: connect one to GND and the other two to two
separate but adjacent universal inputs on the same controller (e.g. U1, U2,
GND, or U4, U5, GND).
J5
J1
Key
Controller terminals
U1
U2
GND
U4
U5
GND
Connecting active temperature and humidity probes
For information on the maximum number of probes that can be
connected see the table at the beginning of this paragraph. The number
depends on the power supply used. The distinction is between probes
powered by the controller (terminal +VDC) and probes powered by an
external source, and also between active probes with voltage or current
outputs. For details on the operating range see the data sheets supplied
with the probes.
The controller can be connected to all the CAREL DP* series active temperature
and humidity probes confi gured at 0 to 1 V or 4 to 20 mA.
J5
Important: For temperature probes use the 4 to 20 mA or NTC
confi guration, as the 0 to 1 Vdc signal is limited to the 0 to 1 V range and is
therefore not always compatible with the standard 10 mV/°C signal of CAREL
probes (at temperatures below 0 °C or above 100 °C a probe alarm may be
triggered).
J1
Key
Controller terminals
GND
+VDC
U1
U2
27
FieldBus card
B M S card
J24
J2
J3
J4
Fig. 5.d
PT100 probe
1
2
Wire 1
Wire 2
Wire 3
Wire 1
Wire 2
Wire 3
FieldBus card
B M S card
J4
J24
J2
J3
Fig. 5.e
Probe terminals
Description
M
Reference
+(G)
Probe power supply
outH
Humidity probe output
outT
Temperature probe output
pCO5plus +0300020EN rel. 1.2 - 07.11.2013