Input/Output Labels - Carel pCO5+ User Manual

Programmable controller
Table of Contents

Advertisement

B.2 Distance 50< L< 200 m.
Use 3 TCONN6J000 boards connected as shown in the fi gure.
L < 200 m
6 5 4 3 2 1 0
Graphic
menu
I/O
set
prog.
?
on/of f
alarm
enter
info
Fig. 4.n
B.3 Distance 200< L< 500 m.
If one of the terminals is connected at a distance >200 m, connect it
according to the layout described in A.3. Connect the other terminal as
described in A.1 or A.2. If both terminals are close to a distance >200 m,
connect them as shown in the layout below.
AWG20/22
alimentatore
+
1 twisted pair
power supply
-
20...30 Vdc -150 mA
6 5 4 3 2 1 0
J14 and J15 on 2-3
on TCONN6J000
Graphic
menu
?
info
menu
I/O
set
prog.
?
on/of f
alarm
enter
info
Fig. 4.o
Case C: 3 terminals
For the fi rst 2 terminals refer to Case B. For the third terminal use one of
connections A.1, A.2 or A.3.
Important :
except for pGD1, the other terminals should be always powered by
separate power supplies;
the 24 Vdc on the +Vterm (J24) terminal can be used only in alternative
to connector J10 to power an external terminal, with maximum current
1.5 W;
in networks with star layout, if the cable is longer than 5 m connect
the terminal only to the fi rst or last pCO5+ in the network (to avoid
branches).
The following table applies.
Type of
MAX distance
cable
controller-terminal (m)
1 Telephone
50
AWG24
2
200
shielded
AWG20/22
3
500
shielded
L < 200 m
6 5 4 3 2 1 0
6 5 4 3 2 1 0
Graphic
menu
I/O
set
prog.
on/of f
alarm
enter
?
info
J1 1 pLAN
J10
L < 500 m
J1 1 pLAN
J31
J10
J1
J24
J2
Graphic
I/O
set
prog.
on/of f
alarm
enter
Board TCON-
Power supply
N6J000 used
Provided by con-
NO
troller (150 mA)
Provided by con-
YES
troller (150 mA)
Separate
YES
Tab. 4.c
2: pCO controller in pLAN network
If a terminal is connected to a pCO controller which is itself connected
to other controllers in a pLAN network, the terminal is directly powered
by the controller. Be sure to avoid the terminal being powered by two
power supplies. For that purpose, set jumpers J14 and J15 on board
TCONN6J000 to interrupt the supply current.
Term 1
Term 2
J14/ J15 ON 2-3
no 30V=
T
T
A
sc
B
AWG24
C
(2 twisted pair)
J1 1 pLAN
J10
J1
J24
J2
When setting up a pLAN network with pCO controllers and terminals,
each pCO5+ controller can power only 1 PGD1/E terminal (except for the
Small model, which can power 2 terminals). When you need to connect
more than one terminal, you will have to provide an independent power
supply. See instructions sheet code +050002895.

4.6 Input/output labels

pCO5+ controllers are distinguished by size and provided with inputs
and outputs and power supplies for the active probes most suitable for
various applications.
The features that depend on the model are:
maximum number and type of inputs/outputs;
availability of built-in driver for expansion valves.
Label
Type of signal
U...
Universal inputs/outputs, confi gurable via software as:
Analogue inputs:
- NTC, PTC, PT500, PT1000 sensors
- PT100 sensors
- 0 to1 Vdc or 0 to 10 Vdc signals
- 0/4 to 20 mA signals
- 0 to 5 V signals for ratiometric probes
Digital inputs (not optically isolated):
- potential-free contacts (not optically isolated)
- fast digital inputs
Analogue outputs (not optically isolated):
- 0 to 10 Vdc signals
- PWM signals
Y...
0 to 10 Vdc analogue outputs, PWM outputs
ID...
24 Vac/24 Vdc digital input
ID...H
230 Vac digital input
NO...
Relay output, normally open contact
NC...
Relay output, normally closed contact
C...
Relay output, common
Tx/Rx, GND Serial port
19
Term n+ 1
Term n
J14/ J15 ON 2-3
J14/ J15 ON 1-2
no 30V=
T
A
A
sc
sc
B
B
AWG24
C
C
AWG24
(3 twisted pair)
(2 twisted pair)
J1 1 pLAN
J1 1 pLAN
J10
J10
J1
J24
J1
J24
J2
Fig. 4.p
pCO5plus +0300020EN rel. 1.2 - 07.11.2013
ENG
30V=
J2
Tab. 4.d

Hide quick links: