Serial ports
for +/- use AWG 20-22 twisted pair shielded
cable
(*): both models are available;(**): confi gurable port J26: see par. 3.2.
Note: In industrial/residential applications with distances greater than 10 m, use
shielded cable with earthed shield.
In domestic applications (EN 55014), regardless of cable length, in versions without
valve driver, the connection cable between controller and terminal and the serial cable
must be shielded and earthed on both sides.
Model with driver for electronic expansion valve
CAREL: E*V****
ALCO: EX4; EX5; EX6; EX7; EX8 330 Hz (recommended by CAREL); EX8 500 Hz (as per ALCO specifi cations)
SPORLAN: SEI 0.5-11; SER 1.5-20; SEI 30; SEI 50; SEH 100; SEH175
Valve compatibility
Danfoss: ETS 12.5-25B; ETS 50B; ETS 100B; ETS 250; ETS 400
CAREL: Two CAREL EXVs as for EVD EVOLUTION TWIN
SPORLAN: SER(I) G, J, K
Shielded 4-wire cable CAREL code E2VCABS*00, or AWG22 shielded 4-wire cable Lmax =10 m, or AWG14 shielded 4-wire cable Lmax = 50
Motor connection
m
Digital input
Digital input to be activated with voltage-free contact or transistor to GND.
connection
Making current 5mA; max. length <10 m.
Max. length 10 m or up to 30 m with shielded cable
S1 Ratiometric pressure probe (0 to 5 V) Resolution 0,1 % fs
Resolution 0.1% fs
Measurement error: 2% fs maximum;
1% typical
Electronic pressure probe (4 to 20 mA) Resolution 0,5 % fs
S2 Low temperature NTC
High temperature NTC
Combined NTC
0 to 10 V input (max. 12 V)
Probes
S3 Ratiometric pressure probe (0 to 5 V) Resolution 0,1 % fs
Electronic pressure probe (4 to 20
mA)
Combined ratiometric pressure probe
(0 to 5 V)
4 to 20 mA input (max. 24 mA)
S4 Low temperature NTC
High temperature NTC
Combined NTC
Power to active
Programmable output: +5 Vdc ±2% or 12 Vdc ±10%, Imax = 50 mA
probes (VREF)
Optional Ultracapacitor module (PCOS0WUC20 or EVD0000UC0). If the controller works constantly at temperatures near the upper limit
Emergency power
of 60°C it is recommended to use the external module code EVD0000UC0, if possible placed in the coolest point of the panel. Modules
supply
PCOS0WUC20 and EVD0000UC0 can be connected to the same controller at the same time, thereby doubling the energy available for
closing the valves. Important: The module only powers the valve driver and not the controller.
Serial
Type/Connectors Characteristics
Serial 0
pLAN/J10, J11
• Built into main board
• HW driver: asynchronous half duplex RS485 pLAN
• Not optically isolated
• Connectors: 6-pin telephone jack + 3-pin plug-in connector p. 5.08
• Max. length: 500 m
• Max. data rate: 115200 bit/s
• Max. number of devices connectable: 32
Serial ONE
BMS 1 Serial Card • Not built into main board
• HW driver: not present
• Can be used with all optional BMS cards of the pCO family
Serial TWO
FieldBus 1 Serial
• Not built into main board
Card
• HW driver: not present
• Can be used with all optional Fieldbus cards of the pCO family
Serial THREE BMS 2 / J25
• Built into main board
• HW driver: asynchronous half duplex RS485 slave
• Optically-isolated/non-optically-isolated serial(*)
• 3-pin plug-in connector p. 5.08
• Max. length: 1000 m
• Max. data rate: 38400 bit/s
• Max. number of devices connectable: 16
Serial FOUR Fieldbus 2/J26
• Built into main board
(and J23 on Large
• HW driver: asynchronous half duplex RS485 master/slave(**)
and Extralarge
• J23: not optically isolated
versions)
• J26: optically isolated/not optically isolated
• 3-pin plug-in connector p. 5.08
• J23 and J26 are both managed by the same protocol as serial 4, with the
advantage of being electrically independent.
Resolution 0,5 % fs
Resolution 0,1 % fs
10 kΩ a 25 °C, -50T90 °C errore di misura: 1°C nel range -50T50 °C; 3°C nel range +50T90 °C
50 kΩ a 25 °C,-40T150 °C Measurement error: 1.5 °C in the range -20T115°C, 4 °C in the range
10 kΩ a 25 °C,-40T120 °C Measurement error: 1°C in the range -40T50 °C; 3°C in the range
Resolution 0,1 % fs
Resolution 0,5 % fs
Resolution 0,1 % fs
Resolution 0,5 % fs
10 kΩ a 25 °C,-50T105 °C; Measurement error: 1 °C in the range -50T50 °C; 3°C in the range
10 kΩ a 25 °C,-40T150 °C Measurement error: 1.5 °C in the range -20T115 °C; 4 °C in the range
10 kΩ a 25 °C, -40T120 °C Measurement error 1 °C in the range -40T50 °C; 3°C in the range
49
Measurement error: 2% fs maximum; 1% typical
Measurement error: 8% fs maximum; 7% typical
Measurement error: 2% fs maximum; 1% typical
Measurement error: 8% fs maximum; 7% typical
outside of -20T115 °C
+50T90 °C
Measurement error: 9% fs maximum; 8% typical
Measurement error: 2% fs maximum; 1% typical
Measurement error: 9% fs maximum; 8% typical
Measurement error: 2% fs maximum; 1% typical
Measurement error: 9% fs maximum; 8% typical
50T90 °C
outside of -20T115 °C
+50T90 °C
pCO5plus +0300020EN rel. 1.2 - 07.11.2013