ONLINE MODULE CHANGE
10.3

Procedures of Online Module Change

This section explains the procedures of online module change when an initial setting of GX
Configurator-AD or GX Configurator-DA is configured and when the initial setting is not
configured.
10.3.1
(1) Disabling conversion
10.3.1 When the initial setting has been configured with GX Configurator-AD or GX Configurator-DA
Table 10.2 Procedures of online module change
Initial setting
GX Configurator-AD or GX Configurator-DA
Sequence program
When the initial setting has been configured with GX Configurator-
AD or GX Configurator-DA
(a) Take the following steps to disable the conversion:
1) Set CH1 A/D conversion enable/disable (Un\G0) and CH5 D/A conversion
enable/disable (Un\G800) to Disable (1).
2) Turn Operating condition setting request (Y9) from off to on to stop the
conversion.
3) Operating condition setting completed flag (X9) turns off from on.
4) Check that CH1 A/D conversion completed flag (Un\G113) is in a status of
Conversion stop (0) and the conversion is stopped by seeing the actual analog
output value.
5) Turn Operating condition setting request (Y9) from on to off.