10
ONLINE MODULE CHANGE
(5) Restarting control
10.3.1 When the initial setting has been configured with GX Configurator-AD or GX Configurator-DA
(d) Set CH1 A/D conversion enable/disable setting (Un\G0) or CH5 D/A conversion
enable/disable setting (Un\G800) to "Enable" (0) and turn off and then on
Operating condition setting request (Y9).
1) A/D conversion (CH1 to CH4)
Monitor CH1 Digital output value (Un\G100) to check if A/D conversion is
properly performed.
2) D/A conversion (CH5 and CH6)
Set CH5 Digital input value (Un\G802) and turn off and then on CH5 Output
enable/disable flag (Y5) to check if D/A conversion is properly performed.
(Be careful since analog values will be output.)
(a) After redisplaying the "Online module change" dialog box by selecting
[Diagnostics]
[Online module change] of GX Developer, click the
button to restart controls such as I/O, FROM/TO instruction executions, and
automatic refresh for the module.
Figure 10.10 "Online module change" (restart of module control) dialog box
Figure 10.9 "Monitor/Test" window
10.3 Procedures of Online Module Change
9
10
11
Execution
10
- 8