FUNCTION
4.2.4

Shifting function (A/D conversion)

The shifting function adds a setting quantity to a digital output value (shifting a digital
output value) and stores the value into buffer memory.
(1) Overview
(a) The shifted output values are stored into CH1 Scaling value (Un\G102).
(b) The shifting amount to conversion value can be set within the range from -32768
(c) Changing the shifting amount to conversion value reflects the scaling value in real
(d) If a scaling function (for A/D conversion) is used simultaneously, the value that is
(2) Setting methods
(a) Set the quantity to be shifted by using CH1 Shifting amount to conversion value
(b) Shifting quantities are added to the digital output value set with CH1 Digital output
(c) The default of shifting amount to conversion value is 0.
(d) If a value is written to a shifting amount to conversion value, regardless of whether
to 32767.
time. Therefore, the digital output value can be adjusted with the shifting function
when the CPU is powered on.
made scaling processing will be shifted.
(Un\G13).
value (Un\G100) every sampling period, and then the added value is stored into
CH1 Scaling value (Un\G102).
Operating condition setting request (Y9) is set to on or off, the shifting amount to
conversion value will be added every sampling period.
4.2 Function Details of A/D Conversion
4.2.4 Shifting function (A/D conversion)