Auto Refresh Setting - Mitsubishi Electric Q64AD2DA User Manual

Analog input/output module
Table of Contents

Advertisement

8
UTILITY PACKAGE (GX Configurator-AD/GX
Configurator-DA)
8.5

Auto Refresh Setting

[Purpose]
Set buffer memory of the Q64AD2DA to be auto-refreshed.
[Operating procedure]
Input "Start I/O No."
Click the
[Setting window]
[Description]
(1) Display items
Module side Buffer
size
Module size Transfer
word count
Transfer direction
PLC side Device
*1
.
Select "Module type".
button.
Auto refresh
* 1 Input a start I/O number in hexadecimal.
Figure 8.8 "Auto refresh setting" window
: Displays the transferable buffer memory size of the setting
item (fixed at one word).
: Displays the number of words that are transferred, starting
from a device set at "PLC side Device" (fixed at one word).
: " " indicates that data are written from the device to the
buffer memory.
" " indicates that data are read from the buffer memory to
the device.
: Input a CPU module device to be auto-refreshed.
Usable devices are X, Y, M, L, B, T, C, ST, D, W, R, and ZR.
When using a bit device, X, Y, M, L, or B, set a number that
can be divided by 16 points (example: X10, Y120, M16).
Buffer memory data are stored by 16 points, starting from
the device whose number was specified.
For example, if X10 is set, data are stored X10 to X1F.
Select "Module model name".
8.5 Auto Refresh Setting