1MRS756378 D
3.3.3.3
REF615
Application Manual
Two separate TCS functions have been included: TCSSCBR1 for PO3 (X100:16-19)
and TCSSCBR2 for PO4 (X100:20-23). Both functions are blocked by the Master
Trip and the circuit breaker open position signal. The TCS alarm indication is
connected to LED 9.

Functional diagrams for control and interlocking

A071326 V4 EN
Figure 14:
Master trip
The operate signals from the protections described above are connected to the two
trip output contacts PO3 (X100:16-19) and PO4 (X100:20-23) via the corresponding
Master Trips TRPPTRC1 and TRPPTRC2. The open control commands to the circuit
breaker from local or remote CBXCBR1-exe_op or from the auto-recloser
DARREC1-open_cb are connected directly to the output PO3 (X100:16-19).
The TRPPTRC1 and 2 blocks provide the lockout/latching function, event generation
and the trip signal duration setting. If the lockout operation mode is selected, one
binary input can be re-assigned to the RST_LKOUT input of the Master Trip to enable
external reset with a push button.
Section 3
REF615 variants
43