ABB REF615 Applications Manual page 137

Feeder protection and control
Hide thumbs Also See for REF615:
Table of Contents

Advertisement

1MRS756378 D
REF615
Application Manual
To enable active setting group changing via binary input, connect any of the (free)
binary inputs to SGCB-block input named ActSG using PCM600 and set the setting
SG follow input to "TRUE".
Table 56:
Active setting group binary input state
BI state
OFF
ON
The setting group parameter is overridden when a binary input is used for changing
the active setting group.
Table 57:
Settings
Parameter
Setting
Setting group
Active group
Not all parameters belong to a setting group. For example protection function enable/
disable settings are not part of a setting group.
Active setting group
1
2
Value
Default
1...4
1
Section 4
Basic functions
Description
Access rights
Selected
RWRW
active group
131