ABB REF615 Applications Manual page 97

Feeder protection and control
Hide thumbs Also See for REF615:
Table of Contents

Advertisement

1MRS756378 D
REF615
Application Manual
GUID-4DED2926-A92A-4F6A-BCAA-7D9CD24ACFC8 V1 EN
Figure 48:
Circuit breaker control
The binary inputs 5 and 6 of the additional card X110 are used for busbar disconnector
(DCSXSWI1) or circuit breaker truck position indication.
Table 19:
Device positions indicated by binary inputs 5 and 6
Primary device position
Busbar disconnector closed
Busbar disconnector open
CB truck in service position
CB truck in test position
The binary inputs 7 and 8 (X110:11-13) are for the position indication of the line side
earthing switch.
The circuit breaker closing is enabled when the ENA_CLOSE input is activated. The
input can be activated by the configuration logic, which is a combination of the
disconnector or breaker truck and earthing switch position statuses and the statuses
of the master trip logics and gas pressure alarm and circuit breaker spring charging.
The OKPOS output from the DCSXSWI block defines if the disconnector or breaker
truck is definitely either open/in test position or close/in service position. This,
Input to be energized
Input 5 (X110:8-9)
X
X
Section 3
REF615 variants
Input 6 (X110:10-9)
X
X
91